Page 16 of 32 of European Technical Assessment no. 23/0482, issued on 2023-09-05
dimos anchor UNI-RT 12, dimos anchor UNI-RT 16: Installation instruction (in concrete or
solid masonry)
Installation in concrete or solid brick:
RECA dimos anchor UNI-RT 12, RECA dimos anchor UNI-RT 16
Intended use
Installation instruction in solid base material
5. Attach the mixing nozzle extension VM-X to the
mixing nozzle VM-XL:
Squeeze out the injection mortar until the mortar has a
uniform grey mixing colour - discard the pre-run of at
least 3 pumps (approx. 10 cm) for coaxial cartridges or at
least 6 pumps for 300ml tubular film cartridges.
6. Fill the drill hole with injection mortar (start from the
bottom of drill hole)
UNI-RT 12:
UNI-RT 16
Important: Follow the installation instructions and
processing time of the injection mortar used in accordance
with the approval/assessment.
7. Insert the hexagon bit (included in the set)
into the M12 threaded stud and screw in the RECA dimos
anchor UNI-RT using a cordless screwdriver until the seal is
pressed firmly against the plaster. A standard
cordless screwdriver is sufficient for this.
Note: The thermal separation module drills itself through the
insulation. The foamed EPDM sealing ring ensures
optimum sealing and can prevent driving rain from entering
the insulation. For details on impermeability to
driving rain see ETA and/or point 10.
8. Observe the curing time of the injection system, see
cartridge label of the injection mortar
9. Afterwards, the attachment can be mounted (max.
torque Tinst = 25 Nm).
Note: Observe an eventually varying installation torque in
the ETA approval of the used injection system.
Note: The screw insertion depth of the M12 threaded stud
in the RECA dimos anchor UNI-RT is min. 30 mm,
max. 34 mm. This means that it may be unscrewed by max.
4 mm - this corresponds to approx. 2 turns.
a ≤ 3,5 mm
1)
Annex B6