Safe Use Instructions – Emerson FB3000 RTU
Part D301876X012
November 2023
Specifications
POWER
Operating Range:
Field Supply: 5 A at 10.5 Vdc to 30 Vdc
Controller Supply: 5 A at 10.5 Vdc to 30 Vdc
ENVIRONMENTAL
Operating Temperature:
Increased Safety (Ex ec): –40 °C to +75 °C
Storage Temp.: –40 °C to +85 °C
Operating Humidity: 5-95 % non-condensing per
IEC 68-2-3.
WEIGHT
1.65 kg (3.675 lbs) (for housing, backplane, and CPU)
APPROVALS
Evaluated to the following European Standards
(EMC):
Emissions
EN 55011:2009+A1:2010
EN 55032:2012
FCC Part 15.019(g):2018 ICES-003 Issue 6
(Emissions)
Immunity
EN 61326-1:2013
EN 61000-4-2:2009 (Electrostatic Discharge)
EN 61000-4-3:2006+A1:2008+A2:2010 (Radiated
EMC Field)
EN 61000-4-4:2012 (Fast Transients/Burst)
EN 61000-4-5:2006 (Surges)
EN 61000-4-6:2009 (Conducted RF)
EN 61000-4-8:2010 (Power Frequency Magnetic
Field)
EN 61000-4-11:2004 (Voltage Dips/Interruptions)
Evaluated to the following Approval Standards
(ATEX/UKCA):
EN IEC 60079-0:2018
EN 60079-7:2015/A1:2018
Evaluated to the following Standards (IEC):
IEC 60079-0:2017 Edition 7.0
IEC 60079-7:2017 Edition 5.1
Product Markings for Hazardous Locations:
Ex ec IIC T4 Gc (Tamb = –40 °C to +75 °C)
II 3 G
SIRA 19ATEX3013X
IECEx CSA 19.0003X
UKCA Cert #CSAE 22UKEX1124X
2
DANGER
When installing units in a hazardous area, make
sure all installation components selected are
labeled for use in such areas. Installation and
maintenance must be performed only when the
area is known to be non-hazardous. Installation or
maintenance in a hazardous area could result in
personal injury or property damage.
Always turn off the power to the FB3000 before you
attempt any type of wiring. Wiring of powered
equipment could result in personal injury or
property damage.
To avoid circuit damage when working inside the
unit, use appropriate electrostatic discharge
precautions, such as wearing a grounded wrist strap.
Check the input power polarity before connecting
power to the FB3000. Wiring of powered equipment
could result in personal injury or property damage.
The following tools are required for installation,
maintenance, and troubleshooting:
Personal computer running Microsoft
Windows
®
7 Professional or Windows 8.1 Pro or
Windows 10 Pro and Emerson Field Tools
configuration software (providing FBxConnect™).
#1 and #2 Phillips (cross-head) screwdriver.
3 mm (1/8-inch) flat-head screwdriver.
Unpacking
You receive the FB3000 in a box. Remove it from the
box. Examine the packing list carefully to ensure you
have all components.
Installation
Note: Do not install the FB3000 vertically.
1. Find a suitable location for the FB3000. When
selecting an installation site, be sure to check all
clearances.
www.Emerson.com/SCADAforEnergy
®