Herunterladen Diese Seite drucken
Emerson EXD-U00 Einbauanleitung
Emerson EXD-U00 Einbauanleitung

Emerson EXD-U00 Einbauanleitung

Schrittmotorsteuerung für elektrische regelventile ex4 - ex8

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 2
EXD-U00 Universal Driver Module is for driving
Emerson stepper motor driven electrical control
valves series EX4/EX5/EX6/EX7/EX8.
!
Safety instructions:
• Read operating instruction thoroughly. Failure
to comply can result in device failure, system
damage or personal injury.
• It is intended for use by persons having the
appropriate knowledge and skill.
• Switch off all voltages / currents before cabling.
• Comply with local electrical regulations when
wiring.
• Do not operate system before all cable
connections are completed.
• Do not apply 110/220/230V to any terminal of
driver module
Setting
Do not apply voltage to the driver before
completion of wiring and setting of dip switches.
Universal
driver
needs
no
configuration by means of dip switches for
application of different valve, different analogue
input signal and type of start mode (see fig. 1).
Function
Dip Switch Number
1 2 3 4 5 6 7 8
EX4/EX5/EX6
0 1 1 0 1 0 - -
EX7
1 0 0 1 0 1 - -
EX8
1 1 0 1 1 1 - -
4-20mA analogue input signal - - - - - - - 0
0-10V analogue input signal
- - - - - - - 1
With start mode (Fig.3b)
- - - - - - 1 -
Without start mode (Fig.3a)
- - - - - - 0 -
Installation and wiring
• Install electrical control valve in system according
to operating instructions of valve. For hot gas
bypass applications install the valve as far as
possible from discharge valve of compressor. Inlet
EXD-U_65072__R05.doc
Universal Driver Module EXD-U00
for Electrical Control Valves EX4 ... EX8
gas temperature to the valve should not exceed
80°C. Contact Emerson for higher temperatures.
Warning: Install valve with electrical
connector in downward position.
• Install Driver Module and other external electronic
devices which need to be connected to driver.
• Set-up all wire connections as shown in wiring
diagram (see Fig. 2).
• Keep separate the wires for power supply, stepper
motor of valve and signal.
• Recommended wire cross section between 0.5
2
mm
and 2.5 mm
Start-up procedure
• Do not apply voltage to the driver before
completion of wiring and setting of dip switches.
• Do not operate the driver and valve when the
system is under vacuum or without refrigerant
except for closing valve before charging of system.
• Vacuum the entire system.
• Warning: The valves are delivered at half open
position. Do not charge system before closure of
setting
except
valve in case of expansion valve and hot gas
bypass application.
• To close valve apply supply voltage to driver
module for the following times without applying
digital input signal 24V to terminals of EXD-U00:
Valve
EX4/EX5/EX6
EX7/EX8
• After closure of valve, interrupt power supply to
driver module and charge the system with
refrigerant.
• Start the system and check operating conditions.
Valve Synchronisation:
Stepper motor driven valves are synchronized with
the reference point in the fully closed position and
the controller is reset when the digital input is open.
For synchronisation the digital input must be
interrupted for 10 sec, at least once a week.
Operating Instructions
2
.
Time, seconds
min: 2
max: 30
min: 6
max: 30
Date: 25.09.2008
Technical data, power supply:
• Main supply voltage: 24V AC/DC (+10%, -15%),
50-60Hz. Power supply line to driver to be
protected by 1.0A external fuse.
• Use a safety class II transformer. Minimum power
required 20VA.
• Emergency supply voltage Ub (from ECP-024):
+18 Vdc.
Inputs:
• 1 analogue input 4-20mA, burden 364Ω, or 1
analogue input 0-10V, impedance 27kΩ.
• 1 Digital input: 24VAC/DC (+10%, -15%), 50-
60Hz.
Outputs:
4 current outputs for stepper motor of EX4 / EX5 /
EX6 / EX7 / EX8.
Nominal current: 0.5A for EX4 / EX5 / EX6,
0.75A for EX7 and 0.8A for EX8.
Maximum cable length: 6 meter AWG20/22.
Uninterruptible power supply ECP-024
• Power supply voltage: 24 VAC ± 10%
• Power outputs: Two, each +18VDC
Wiring Diagram see Fig. 2
(3) = Fuse 1.0A
(4) = DIN plug for connection to EX8 (prior to
March 2008 production)
(5) = Plug cable assembly EX5-Nxx for connection
to EX4/EX5/EX6/EX7 and EX8(new)
(6) = Controller supplies 4...20mA or 0...10V
(7) = Digital input signal (0V = OFF; 24V = ON)
(8) = Analogue input signal (4...20mA or 0...10V)
(9) = Optional
Uninterruptible
insures the closure of valve during power
failures in systems, where a valve with
positive shut-off function is needed
Cable color code
WH =
White
BK =
Black
BL =
Blue
BN =
Brown
GB
Power
Supply
PCN 864752

Werbung

loading

Inhaltszusammenfassung für Emerson EXD-U00

  • Seite 1 (3) = Fuse 1.0A Function Dip Switch Number digital input signal 24V to terminals of EXD-U00: (4) = DIN plug for connection to EX8 (prior to 1 2 3 4 5 6 7 8 Valve...
  • Seite 2: Sicherheitshinweise

    Regelventilen der überschreiten. Bei höheren Temperaturen wenden • Versorgungsspannung: 24V AC/DC (+10%, -15%), Baureihe EX4/EX5/EX6/EX7/EX8 eingesetzt. Sie sich bitte an Emerson. 50-60Hz (mit 1,0 A absichern) Achtung: Regelventil mit elektrischem Stecker • Transformator Klasse II verwenden, Nennleistung:...
  • Seite 3: Instructions D'installation

    Module d’alimentation universel EXD-U00 pour vannes électronique EX4 … EX8 Instructions d'Installation Le module pilote universel EXD-U00 est conçu pour Contacter Emerson si cette température est Caractéristiques techniques, alimentation alimenter les vannes de détente électroniques supérieure à 80°C. • Alimentation du module: 24V AC (+10%, -15%), EX4/EX5/EX6/EX7/EX8.
  • Seite 4 – napřed se musí uzavřít a pak plnit okruh použití a typu ventilu. Jiné nastavení není zapotřebí. • Napájení modulu bez připojení digivstupu 24V (1) napájení (viz obr.1) (2) trafo k EXD-U00 po dobu : Činnost Číslo mikropřepínače (3) pojistka ventil zpoždění...
  • Seite 5 Uniwersalny moduł sterujący EXD-U00 do elektrycznych zaworów sterujących EX4 … EX8 Instrukcja montażu Uniwersalny moduł sterujący EXD-U00 służy do gazu nie powinna przekraczać 80°C. W przypadku Dane techniczne i zasilanie: napędu elektrycznych zaworów sterujących z silni- wyższych temperatur należy skontaktować się...
  • Seite 6 Универсальный привод серии EXD-U00 для электрических регулирующих вентилей EX4 … EX8 Инструкция по эксплуатации Универсальный привод EXD-U00 предназначен Температура газа на входе в вентиль не должна Технические характеристики, для управления электрическими вентилями превышать 80°C. Применение при температурах электропитание: • Основное напряжение электропитания: 24В...
  • Seite 7 Fig. 3 a Fig, 3 b Fig. 1: Fig. 2: Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 - 71332 Waiblingen - Germany - Phone +49 7151 509-0 - Fax +49 7151 509-200 www.emersonclimate.eu EXD-U_65072__R05.doc Date: 25.09.2008...