Herunterladen Diese Seite drucken

Bosch UGM 2040 Konfiguration Und Bedienung Seite 183

Vorschau ausblenden Andere Handbücher für UGM 2040:

Werbung

UGM 2040
</TOP>
</System>
...
<!-- ********* alle MCX ******************** -->
<System Name="MCX1" Type="MCX">
<MCX IPAddress="192.168.1.101" HostName="MCX1" Port="9005"
ControllerPortName="COM8" DebugPortName="COM7" DisplayName="">
<!-- ********* alle Schnittstellen der BE 2040 ******************** -->
<COMPORT Name="COM1" BaudRate="9600" Databits="7" Parity="EVEN" StopBits="1"
FlowControl="No" PhysicalMode="OPTO" Handshake="4A" Station="B" />
<COMPORT Name="COM2" BaudRate="9600" Databits="7" Parity="EVEN" StopBits="1"
FlowControl="No" PhysicalMode="OPTO" Handshake="4A" Station="B" />
...
<LINE Name="MCX.DT" SampleCount="3" Level1="0" Level2="0" Level3="0"
ResistorModel="E" />
<LINE Name="MCX.GFD" SampleCount="3" Level1="0" Level2="400" Level3="800" />
<LINE Name="MCX.IN1" SampleCount="3" Level1="300" Level2="600" Level3="900" />
<LINE Name="MCX.IN2" SampleCount="3" Level1="300" Level2="600" Level3="900" />
<LINE Name="MCX.IN3" SampleCount="3" Level1="300" Level2="600" Level3="900" />
<LINE Name="MCX.IN4" SampleCount="3" Level1="300" Level2="600" Level3="900" />
...
<CONTACT Name="MCX.OUT1" DefaultPosition="0" />
<CONTACT Name="MCX.OUT2" DefaultPosition="0" />
<CONTACT Name="MCX.OUT3" DefaultPosition="0" />
<CONTACT Name="MCX.OUT4" DefaultPosition="0" />
<BatterySupervision Name="MCX1.BCM1.BatterySupervision2" />
<BatterySupervision Name="MCX1.BCM1.BatterySupervision1" />
<PowersupplySupervision Name="MCX1.BCM1.PowersupplySupervision1" />
<PowerLine Name="MCX1.BCM1.PL2" IMin="200" IMax="500" />
<PowerLine Name="MCX1.BCM1.PL1" IMin="200" IMax="500" />
</MCX>
<!-- ********* alle Geräte an der BE 2040 ******************** -->
<GPIN Name="Türkontakt" AdapterRule="MappingDoorTamperDefault"
UsedDevice="MCX.DT"
EntityType="ContactTamper" DisplayName="Türkontakt (UGM2040)" />
<GPIN Name="Erdschluss" AdapterRule="MappingGroundFaultDefault"
UsedDevice="MCX.GFD"
EntityType="GeneralInput" DisplayName="Erdschluss (UGM2040)" />
<BCM Name="MCX1.BCM1" AdapterRule="MappingGeneralComponentDefault" Slot="1"
DisplayName="BCM Modul 1 (MCX1)" />
<Battery Name="MCX1.Battery1" AdapterRule="MappingBatteryDefault"
UsedDevice="MCX1.BCM1.BatterySupervision1" DisplayName="HHHH" />
<PowerSupplyUnit Name="MCX1.PS1" AdapterRule="MappingPowersupplyDefault"
UsedDevice="MCX1.BCM1.PowersupplySupervision1" DisplayName="Netzteil 1 (MCX1)" />
</System>
...
<!-- ********* Ende alle MCX ******************** -->
...
Bosch Sicherheitssysteme GmbH
Konfiguration und Inbetriebnahme
Konfiguration – Import und Export | de
2012.09 | V 1.0 | F.01U.276.086
183

Werbung