4. OPERATION
4.1. Battery charging
After applying mains power and switching the unit ON:
all LEDs will be lit during two seconds
the green LED will then be on to indicate the unit is "On"
the state of charge will be indicated by lighting one of four yellow LEDs
the actual output voltage and current will be indicated by the appropriate red LED bars
the internal fans may run depending upon the temperature inside the cabinet (temperature controlled)
In case the red LED is lit, refer to section 6.
4.2. Seven stage charge curve for lead-acid batteries
absorption voltage
float voltage
storage voltage
U
100%
I
Equalization
4.2.1. Bulk
Entered when the charger is started (DS-2 on and battery voltage <26 V, or DS-2 off), or when the battery voltage falls below 26.4
V (due to a heavy load) during at least 1 minute. Constant current is applied until gassing voltage is reached (28.8 V for a 24 V
battery).
4.2.2. BatterySafe
If absorption voltage is set higher than 28.8 V, the rate of voltage increase beyond 28.8 V is limited to 14 mV/minute, in order to
prevent excessive gassing.
4.2.3. Absorption
After the absorption voltage has been reached, the charger operates in constant voltage mode.
In case of adaptive charging, the absorption time is dependent on the bulk time, see section 3.3.
4.2.4. Automatic equalization
If automatic equalization has been set to "on", the absorption period is followed by a second voltage limited constant current
period: see section 3.3. This feature will charge VRLA batteries to the full 100 %, and prevent stratification of the electrolyte in
flooded batteries.
Alternatively, manual equalization can be applied.
4.2.5. Float
Float voltage is applied to keep the battery fully charged.
In case of adaptive charging, the float voltage time is dependent on the bulk time, see section 3.3.
4.2.6. Storage
After float charge the output voltage is reduced to storage level. This level is not sufficient to compensate for slow self-discharge
of the battery, but will limit water loss and corrosion of the positive plates to a minimum when the battery is not used.
4.2.7. Weekly battery "refresh"
Once a week the charger will enter Repeated Absorption-mode during one hour to 'refresh' (i. e. to fully charge) the battery.
12
bulk
absorption
Figure 8.
float
storage
time