Multifunction Installation Tester/English
1-When measuring is completed, impedance of
L-PE and PFC (lf) value appears on the screen
2-Press TEST button if re-test is necessary.
When symbol from
,
,
appears lower left corner, and if the voltage
exceeds 260V, the measurement will not take place
5.2.3-Using the Hi Amp LOOP Measurement to be
selected where the circuit is NOT protected by the
inclusion of an RCD
1-Turn the rotary switch to the LOOP / PFC position
2-Press F2 button to change from No Trip to Hi Amp
3-Connect the test leads as shown in the Figure 8
4-If voltage of the L-PE on the lower left appears, the
unit is ready to TEST
5-Press the TEST button when ready
Figure 7 Hi Amp LOOP-To be used where
NO RCD is present
14
Figure 5 No Trip-Measurement completed
Figure 6 Hi Amp Loop-Standby screen
Figure 8 Hi Amp LOOP-Test lead connection
6-When the measuring is complete the impedance
of L-PE and PFC (lf) value appears on the screen
7-Press TEST button if re-test is necessary
When symbol from
,
,
appears lower left corner, and if the voltage
exceeds 260V, the measurement will not take place
5.2.4-Using the L-N Line Impedance Measurement
1-Turn the rotary switch to the LOOP / Psc position
2-Press F1 button to change from L - PE to L-N
3-Connect the test leads as shown in Figure 12
4-If voltage of the L-PE on the lower left appears, the
unit is ready to TEST
5-Press the TEST button when ready
Figure 11 N Line Impedance-When measuring
Multifunction Installation Tester/English
Figure 9 Hi Amp LOOP-Measurement nished
Figure 10 L-N Line-Standby screen
Figure 12 N Line Impedance-Test Ieads
connection
15