RS Pro RS MT-6600 Bedienungsanleitung Seite 3

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Multifunction Installation Tester/English
1.4-Caution
Do not change functions on the test instrument with the test le
to a test where the supply is required could damage the instrument.
1.5-Declaration of Conformity
This instrument has been tested according to the below regulations:
EN 61326: Electrical equipment for measurement, control and lab
EN 61010-1: Safety requirements for electrical equipment for me
–Part 1: General requirements.
BS EN61557: Electrical safety in low voltage distribution syste
Equipment for testing, measuring or monitoring of protective measures.
• Part 1 General requirements
• Part 2 Insulation resistance
• Part 3 Loop resistance
• Part 4 Resistance of earth connection and equipotential bondi
• Part 6 Residual current devices (RCDs) in TT and TN systems
• Part 7 Phase sequence
• Part 10 Combined measuring equipment
1.6-Error Codes
Various error conditions are detected by the tester and are indicated with the icon, "Err", and an error
number on the primary display. See Table 1. These error conditions disable testing and, if necessary, stop
a running test.
Table 1. Error Codes
Error Condition Code
Code
Solution
Solution
1
Check the installation, in particular, the voltage
Fault Voltage
between N and PE.
Over Temp
2
Wait while the tester cools down.
Excessive Noise
Switch o all appliances (Loop, RCD measurements)
3
and move the earth stakes (earth measurement).
Excessive Probe
4
Put the stakes deeper into the soil. Tamp down the
Resistance
soil directly around the stakes. Pour water around
the stakes but not at the earth ground under test.
Self Test Fails
Return the tester to a Service Center.
5
2-Speci cation
LOOP Resistance
L- PE (Hi-Amp)
Range( )
Resolution( )
Accuracy
0.23 9.99
0.01
±(4% of reading+6digits)
10.0~99.9
0.1
100~999
1
Measuring Current: 8.0 A~25.0 A
Range of the Voltage Used: 195V a.c. – 260V a.c. (50,60Hz)
2
ads in place, i.e. changing from a "dead test"
oratory use.
asurement, control and laboratory use
ms up to 1000V a.c. and 1500V d.c.
ng
.
Notes
[1] Valid for resistance of neutral circuit <20
and up to a system phase angle of 30°. Test leads must be zeroed
before testing.
[2] Valid for mains voltage >200V.
L- PE (No Trip)
Range( )
Resolution( )
Accuracy
0.23 9.99
0.01
±(5% of reading+6 digits)
10.0~99.9
0.1
100~999
1
Measuring Current: < 15mA
Range of the Voltage Used: 195V a.c – 260V a.c (50,60Hz)(50,60Hz)
Notes
1] Valid for resistance of neutral circuit <20
and up to a system phase angle of 30°. Test leads must be zeroed
before testing.
[2] Valid for mains voltage >200V.
LINE Resistance
L- N
Range( )
Resolution( )
Accuracy
0.23 9.99
0.01
±(4% of reading+4digits)
10.0~99.9
0.1
100~999
1
Measuring Current: 4.0 A
Range of the Voltage Used: 195V a.c. – 260V a.c. (50,60Hz)
Notes
[1] Valid for resistance of neutral circuit <20
and up to a system phase angle of 30°. Test leads must be zeroed
before testing.
[2] Valid for mains voltage >200V.
RCD (BSEN 61557-6)
Rcd Rating (I_n): 10mA, 30mA, 100mA, 300mA, 500mA, 650mA and 1A
Test current: x1/2, x1, x2 and x5
Multifunction Installation Tester/English
.
3

Werbung

loading