Multifunction Installation Tester/English
6-When measuring is completed, impedance of
L-N and PSC value appears on the screen
7-Press TEST button if re-test is necessary
When symbol from
,
,
appears lower left corner, and if the voltage
exceeds 260V, the measurement will not take place
5.2.5-Using The RCD Function
You can select UL Voltage by Pressing and hold
F3 button for more than two seconds (25V or 50V).
Uf value appears is the contact voltage on the
screen.
16
Figure 13 L-N Line Impedance-Measurement
completed
Figure 14 RCD-Standby screen
Function Button Description
BUTTON
F1
AUTO
RCD t
RCD I N
F2
30mA
100mA
300mA
500mA
F3
AC G
AC S
F4
0
180
G: General (non-delayed) RCDs
S: Selective (time-delayed) RCDs
Possible setup ratios depending on the RCD Trip Current
X1/2
X1
X2
X5
AUTO
RAMP
Maximum measurement Trip Time of the RCD (Complying to BS 61008 and 61009)
General
t =
t =
t =
(non-delayed)
Max.1999mS
Max.500mS
Max.150mS
RCD
Selective
t =
t =
t =
(time-delayed)
Max.1999mS
Max.500mS
Max.150mS
RCDs
I N: Trip-Out Current
t : Trip-Out Time
: Indicates that the thermal protection device has operated and
Instrument must be allowed to cool for a period before tests can continue.
Multifunction Installation Tester/English
650mA
1A
10mA
t = Max.40mS
t = Max.40mS
therefore cannot make any measurements.
17