Multifunction Installation Tester/English
5.2.1-Using the No Trip LOOP Measurement to be selected where the circuit is protected by an RCD whose
rating is 30mA or above
1-Turn the rotary switch to the LOOP/PFC position
2-Connect the test leads as Figure Figure 4
3-If voltage of the L- PE on the lower left appears, the
unit is ready to TEST
4-Press the TEST button when ready
5-If NOISE appears during the No Trip Loop
Measurement, the displayed value may not be
accurate due to "mains" interference and the
test should be repeated
When carrying out the test from a 13A socket
the points of contact are automatically selected by
the plug top connection
12
Figure 2-No Trip LOOP-Standby Screen
Ω
A
Figure 3-No Trip LOOP
Figure 4 No Trip LOOP-Test lead connection
5.2.2-LOOP / PFC Function Menu Operation
Main Display
Menu Display
F1 Button: Pop-up and shutdown Loop/PFC menu, Shutdown mode is activated
F2 Button: Pop-up and shutdown Current menu, Shutdown mode is activated w
F3 Button: None
F4 Button: Press the F4 button 3S, triggering zero function.
Up Button: Up menu to select the current active sub-options.
Down Button: Down menu to select the current active sub-options.
Enter Button: Con rm the user select mode.
Multifunction Installation Tester/English
when the user selects.
hen the user selects
13