- The external sensor is used as deported ambient sensor to
regulate the temperature of the room.
Amb. + Limit 1
- The programmer will regulate the temperature in the room with
the internal sensor the external sensor is used as floor limiter.
- Two new values will be appears:
Lower limit: 18.0°C (default value)
The floor will never decrease under this value.
Higher limit: 35°C (default value)
The floor will never overpass this value.
Amb. + Limit 2
- The programmer will regulate the temperature in the room with
the internal sensor the external sensor is used as intelligent floor
limiter.
- One new value will be appears:
Floor Offset: 0°C (default value)
Offset added or subtracted to the actual setting (
temperature following by the thermostat, to define the value of the
lower floor limitation.
4.3.2
In this submenu you must choose the type of regulation which
must be used for the room managed by the programmer.
To change the regulation, move the navigation cursor in front of the
desired line and Press (Ok) to valid "".
On / Off: (Hysteresis)
- Basic regulation with static differential of 0.5°C
PWM: (proportional band)
Panel Heater
- advanced regulation with integral proportional band specially
made for panel heater.
(external sensor is needed 10k at 25°C)
(external sensor is needed 10k at 25°C)
Regulation type
Regulation type
On / Off
 PWM
Panel Heater
Thickness floor >5cm 
Thickness floor <5cm
29