Floor with thickness >5cm
- advanced regulation with integral proportional band specially
made for floor heating with big inertia.
Floor with thickness <5cm
- advanced regulation with integral proportional band specially
made for floor heating with small inertia.
4.3.3
Calibration sensor
In this submenu you can calibrate the sensors.
Procedure for calibration:
- The calibration must be done after 12Hours working with the
same setting temperature.
Ambient sensor calibration:
- To check the temperature in the room, put a thermometer at 1.5M
distance to the floor in the concerned room and wait 1 hour to be
sure that the thermometer show the correct temperature.
Then you can enter the value saw on the thermometer with (◄-) or
(►+) in the corresponding line "Ambient" and press (Ok) to valid.
- When a calibration is made the message "Made" will be
displayed.
- To erase the calibration already made press (Ok) and change the
value "made" by "no" with (◄-) or (►+).
External sensor calibration:
- The calibration must be done same as described above if the
external sensor is connected and used like a deported ambiance
sensor.
- If the external sensor is used as floor sensor, the thermometer
should be put on the floor.
4.3.4
Pump Exercise
Calibration sensor
 Ambient
Floor (ext)
30
no