EN

Wiring diagram

SanTec PROOF P6 – 12 V with TD
Key switch
(without cylinder)
Art. no. 110 418
Power supply:
2 x 0.5 mm
total cable length max. 100 m
2
Power supply, 1-connect.
Power supply, 5-connect.
!
Use the 3-m SanTec power cable
(included in the delivery scope)

Thermal disinfection:

Turning the key switch will cause the entire system to change into thermal disinfection operating
mode. This will disable all other functions, making it impossible to trigger any operations via buttons or
the IR sensor. After a safety delay of 30 s, the first device will execute a disinfection cycle.
This is indicated by a rapidly flashing LED. The bypass magnetic valve is unlocked. The thermal
disinfection takes 12 minutes; however, if shower monitoring (DIP 5 = On) has been enabled, it will be
immediately aborted if a user enters the sensor range. In this case, thermal disinfection will start again
2 minutes after no user has been present in the sensor range.
After closing the bypass valve, a cold water rinse will be performed in any case for 10 s. After this
the LED lights up to indicate that the disinfection cycle has been completed. Next, device 2 starts the
disinfection cycle, followed by device 3 etc.
If you return the key switch to the off position, thermal disinfection is immediately aborted (the device
that was performing a cycle will perform a 10-s cold water rinse).
If you turn the key switch again, thermal disinfection will start again at device 1.
Provide for adequate ventilation to ensure proper operation of the shower monitoring function.
24
Shower control
PROOF P6 with thermal disinfection
Colour legend:
art. no. 117 899
1 ....... Green
art. no. 113 792
2 ....... Yellow
3 ....... White
4 ....... Brown
5 ....... Red
SanTec OCEAN P6 with thermal disinfection
Control line for thermal disinfection
2 x 0.5 mm
2
total cable length max. 100 m
12 V=
12 V=
+ –
+ –
1
2
3 4 5
1
2
3 4 5
Terminal box
Device 1
Device 2
+ –
+ –
1
2
3 4 5
1
2
3 4 5
12 V=
12 V=
+ –
+ –
1
2
3 4 5
1
2
3 4 5
Device 3
Device 4
+ –
+ –
1
2
3 4 5
1
2
3 4 5

Werbung