Siemens SIMATIC S7-1200 Produktinformation Seite 18

Vorschau ausblenden Andere Handbücher für SIMATIC S7-1200:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Overview of the behavior of the F-CPUs regarding communication network disconnectors according to IEC 61784-3-3
(PROFIsafe standard)
F-CPU
CPU 1212FC DC/DC/DC
CPU 1212FC DC/DC/Rly
CPU 1214FC DC/DC/DC
CPU 1214FC DC/DC/Rly
CPU 1215FC DC/DC/DC
CPU 1215FC DC/DC/Rly
CPU 1511(T)F-1 PN
CPU 1513F-1 PN
CPU 1510SP F-1 PN
CPU 1512SP F-1 PN
CPU 1514SP (T)F-2 PN
CPU 1515(T)F-2 PN
CPU 1516(T)F-3 PN/DP
CPU 1517(T)F-3 PN/DP
CPU 1513proF-2 PN
CPU 1516proF-2 PN
CPU 1518(T)F-4 PN/DP
(ODK)
CPU 1518HF-4 PN
CPU 1518F-4 PN/DP MFP
CPU 1505SP (T)F
CPU 1507S F
CPU 1508S F
Absolute network disconnector between socket A and B:
1
a) If A and B belong to different local Ethernet interfaces (for example, X1 and X2) and no bridging is implemented at
communication level 2 for these interfaces.
a) If either A or B are part of a local Ethernet interface and the other is part of a backplane bus module with an Ethernet
interface (CP, CM), and no bridging is implemented at communication level 2 for these interfaces.
No network disconnector between socket A and B:
2
a) If A and B belong to the same local Ethernet interface (for example, X1).
b) If A and B both belong to a backplane bus module (CP, CM).
Even when using a communication network disconnector according to IEC 61784-3-3 (PROFIsafe standard), you must still
ensure that the individual isolated networks are not connected by other standard components. See also this FAQ
(https://support.industry.siemens.com/cs/ww/en/view/109740240).
Standard CPUs are generally not network disconnectors according to IEC 61784-3-3 (PROFIsafe standard).
Support of PROFIsafe V2 for PROFINET IO
Interfaces that support PROFINET IO also support PROFIsafe V2.
Support of PROFIsafe V2.4 for PROFIBUS DP
Interfaces that support PROFIBUS DP also support PROFIsafe V2.4 but not PROFIsafe V2.6.
Restriction with "CREAT_DB" and "DELETE_DB" instructions
F-DBs can neither be created nor deleted.
Restriction with "READ_DBL" and "WRIT_DBL" instructions
The destination address must not point to an F-DB.
18
Network disconnector according to IEC 61784-3-3
Network disconnection between Ethernet X1 and CP/CM on the
backplane bus.
Network disconnection between Ethernet X1 and X2.
Network disconnection between Ethernet X1 and CP/CM on the
backplane bus.
Network disconnection between Ethernet X2 and CP/CM on the
backplane bus.
Network disconnection between Ethernet X1, X2 and X3.
Network disconnection between Ethernet X1 and CP/CM on the
backplane bus.
Network disconnection between Ethernet X2 and CP/CM on the
backplane bus.
Network disconnection between Ethernet X3 and CP/CM on the
backplane bus.
No
Remark
see
and
1
2
F-CPUs
A5E35635424-AM, 11/2022