CPU label
CPU 1516F-3 PN/DP
CPU 1516F-3 PN/DP
CPU 1516F-3 PN/DP
CPU 1513proF-2 PN
CPU 1516proF-2 PN
S7-1500 F
CPU 1516TF-3 PN/DP
CPU 1517F-3 PN/DP
CPU 1517TF-3 PN/DP
CPU 1518F-4 PN/DP
CPU 1518F-4 PN/DP
ODK
CPU 1518F-4 PN/DP
MFP
CPU 1518HF-4 PN
CPU 1518TF-4 PN/DP
Restrictions on the maximum specified ambient air temperature with reference to the installation altitude
Installation altitude
-1 000 to 2 000 m
2 000 to 3 000 m
3 000 to 4 000 m
4 000 to 5 000 m
The basic value for the application of the derating factor is the maximum permissible ambient temperature in °C for
1)
2 000 m
Note
Linear interpolation between altitudes is permissible.
The derating factors compensate for the decreasing cooling effect of air at higher altitudes due to lower density.
Pay attention to the mounting position of the respective module in the technical data. Based on the IEC 61131-2:2017
standard.
Ensure that the power supply units used are also adequate for altitudes > 2 000 m.
The displays of the S7-1500 CPUs are designed for an altitude of ≤ 3 000 m. If used at > 3 000 m, in rare cases, there can
be problems in the representation of the CPU display; however, these do not have an effect on the functional safety of the
F-CPU.
The "Safety-oriented tripping of standard modules" function, as described on the SIEMENS Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/view/39198632) pages, is only approved up to max. 2 000 m.
Effects on the availability
The higher cosmic radiation present during operation at altitudes above 2 000 m will also start to have an effect on the
failure rate of electronic components (the so-called soft error rate). In rare cases, this can result in a transition of the F-CPU
into the safe state. However, the functional safety of the F-CPU is fully retained.
16
Article number
6ES7516-3FN01-0AB0
6ES7516-3FN02-0AB0
6ES7516-3FP03-0AB0
6ES7513-2GL00-0AB0
6ES7516-2GN00-0AB0
6ES7516-3UN00-0AB0
6ES7517-3FP00-0AB0
6ES7517-3UP00-0AB0
6ES7518-4FP00-0AB0
6ES7518-4FP00-3AB0
6ES7518-4FX00-1AB0
6ES7518-4JP00-0AB0
6ES7518-4UP00-0AB0
Ambient temperature
0 to +60
FS 01
-25 to +60
FS 01
-30 to +60
FS 01
-25 to +55
FS 01
-25 to +55
FS 01
0 to +60
FS 05
0 to +60
FS 01
0 to +60
FS 04
0 to +60
FS 01
0 to +60
FS 04
0 to +60
FS 01
0 to +60
FS 01
0 to +60
FS 10
Derating factor for ambient air temperature
1.0
0.9
0.8
0.7
Installation altitude
5 000
FS03 or
higher
5 000
FS01 or
higher
5 000
FS01 or
higher
5 000
FS01 or
higher
5 000
FS02 or
higher
5 000
FS05 or
higher
5 000
FS05 or
higher
5 000
FS05 or
higher
5 000
FS05 or
higher
5 000
FS05 or
higher
5 000
FS01 or
higher
5 000
FS01 or
higher
5 000
FS10 or
higher
1)