Herunterladen Diese Seite drucken

Honeywell Fema DCM-Serie Montage- Und Bedienungsanleitung Seite 65

Druckschalter

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

The following applies for all models:
Changes of the setpoint spindle to the set
the switching pressure do not lead to
changes in the switching intervals; how-
ever, the switching points will translate in
parallel correspondingly.
The switching differential of the individual
microswitches corresponds to the
switching differences listed under basic
equipment.
The switching differential cannot be set for
individual microswitches in two-stage
pressure switches.
The switching points can be moved parallel
to the setting spindle.
MU2B-0238GE51 R0220F
5.
Two-Stage Pressure Switches ...-307, ...-217
5.2 Model ...-217
Both microswitches are connected
internally according to the given wiring
diagram (see label next to the plug
connection). The switching points can be
set with 2 setting spindles within their
designed limits.
The switching differential of the individual
microswitch corresponds to the switching
differentials listed under basic equipment.
25