Honeywell Fema DCM-Serie Montage- Und Bedienungsanleitung Seite 59

Druckschalter

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2.
When the switching differential is changed,
the switching point remains unchanged.
The reset point is shifted by the value of
the switching differential.
CAUTION:
When approaching the max. switching
differential value, take care that the
differential spindle not be turned so far as
to hit the stop and possibly jam, as this
could interfere with switching back. In the
event that this nonetheless accidentally
happens, loosen the screw by a half or full
rotation.
MU2B-0238GE51 R0220F
Pressure Switches with Adjustable Switching Difference ...V...-203
RSP = SP – x
d
Fig. 9.
Rising pressure
RSP = SP – x
d
SP = switching point
RSP = switch back point
x
= switching differential (hysteresis)
d
p = pressure
19