Herunterladen Diese Seite drucken

Daikin Altherma FWXT10ABTV3 Installations- Und Bedienungsanleitung Seite 25

Wärmepumpen-konvektor

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 42
EKWHCTRL1 connections
Connect the RS485 line of the wall-mounted remote control
to one or more (up to a maximum of 30) units through a cable
suitable for RS485 serial connection, keeping it separate
from power supply cables.
Try to inimise the length of the connection cables;
Complete the line with the 120 Ω resistance supplied;
Do not make "star" connections;
The RS485 connection is polarised, observe the
indications "A" and "B" on each peripheral device
connected (for the connection it is preferable to use a
+ A B -
A A B B -
CP
See paragraph 5 on page 30 for the istructions for use with wall-mounted control panel.
shielded cable with a minimum section of 0.35 mm
Connect the + and - power supply terminals of the wall-
mounted terminal, 5 V DC voltage, on one of the
convector boards, respecting the polarities.
N540022B
L
N
N540022B
);
2
EN
25

Werbung

loading