Pay attention to the tilt of the condensate drain pipe when
it channels condensate outside the premises as shown in
the figure.
convector
A
condensate drain pipe
B
A
2.9
Filling system
When
starting
the
system,
lock-shield on the hydraulic unit is open. If there
is
a
power
black-out
2.10
Evacuating the air when filling the system
-
Open all the system's shut-off valves (whether manual
or automatic);
-
Start filling the system by slowly opening the water
tap;
-
With the aid of a screwdriver, open the vent on the
uppermost coil connection (see figure below);
-
When water begins to leak out of the breather valves,
close them and continue to fill the system (as per the
rated specifications).
A
Coil vent
make
sure
that
the
and
the
thermal
valve
B
is already running, use its cap to press the valve shutter
and open it.
Check the tightness of the gaskets.
We recommend that you repeat this operation when the
device has been running for a few hours and that you
regularly check the system's pressure.
A