Herunterladen Inhalt Inhalt Diese Seite drucken

Zodiac DF2 Montage- Und Gebrauchsanleitung Seite 24

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 81
3.3.5 Configuring the test mode
Once the installation of the dehumidifier is finished, the installer can check the appliance in test mode. This mode is
used to force the dehumidification functions (and the heating kit, if installed).
To activate/deactivate the test mode:
• In the "EASY" menu, browse with the
confirm.
• Using the
or
- 0 = stop test mode (default settings)
- 1 = start test mode.
• Press
to confirm.
OK
• Press
to go back to the previous screen.
Press
a number of times to return to the home screen.
• When the test mode is activated, the
To set the test mode duration:
• In the "EASY" menu, browse with the
confirm.
• Using the
or
the duration must be set before running the test mode. Changes to this setting during the test will only be taken
into account later.
• Press
SET
to confirm.
• Press
to go back to the previous screen.
Press
a number of times to return to the home screen.
• If the test mode is manually stopped prematurely ("P30" = 0), the
until "P31" has counted down.
Several checks can be performed in test mode:
• Check that hot air is coming out of the appliance's blower grids.
• Check that the following symbols are displayed:
3.3.6 Understanding Remote ON/OFF
24
or
keys until you reach the "P30" setting, then press
keys, select:
or
keys until you reach the "P30" setting, then press
keys, choose the desired duration (in minutes). The default duration is 30 minutes. Note that
Refer to § 2.6.1 "Terminal block detail" for details on the connection
characteristics.
This input is a DRY CONTACT, and from the factory set to closed by a
shunt. Meaning that the appliance is only managed from the main user
display.
If the user desires to control the appliance with an external DRY
CONTACT, such contact has to be connected in between these
terminals: X9.1 - X9.2.
When these terminals detect an open contact, the appliance will be
OFF, due to this external input, see image on the left.
Once the contact reverts to a closed one, the appliance will revert to
it's prior status.
symbol is displayed.
Dehumidification
to
SET
to
SET
symbol remains on the screen
Heating
or

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis