Herunterladen Inhalt Inhalt Diese Seite drucken

Communication Interfaces - Emerson CSI 6500 Machinery Health Monitor A6110 Schnellstartanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Product Information / Produktinformation A6110
Shaft Vibration Monitor
Alarm outputs
Opto−decoupled collector/emitter segments
Alert channel 1 A1−C / A1−E
Danger channel 1 D1−C / D1−E
Alert channel 2 A2−C / A2−E
Danger channel 2 D2−C / D2−E
Maximum value for alarm outputs
Alarm status of the alarm outputs
Open circuit mode / closed−circuit mode
The digital inputs SC−A and SC−D can be selected with external signals.
Switchover ALERT
Switchover DANGER
Switch level
Input resistance

1.6.4 Communication interfaces

Interface RS 232
Front socket for connecting a laptop / computer for configuration and visualization purposes
Round plug connector on the front
side
Interface RS 485
d4, z4 bus interface for communication with an MMS 68xx epro analysis and diagnostic
system and the configuration software.
b26 (collector) / b28 (emitter)
d26 (collector) / d28 (emitter)
b30 (collector) / b32 (emitter)
d30 (collector) / d32 (emitter)
C−E disabled:
max. perm. U
C−E conductive: max. perm. U
Conducting in open circuit mode, disabled in
closed−circuit mode
d24 − SC−A
= HIGH / blank
= open circuit mode
d24 − SC−A
= LOW = closed−circuit mode
z24 − SC−D
= HIGH / blank
= open circuit mode
z24 − SC−D
= LOW = closed−circuit mode
LOW = 0 ... +3 V
HIGH = 13 ... 48 V
> 10 kΩ
Mini DIN socket type TM 0508A/6 for parameterization
cable (included in the operating kit)
Page 19