Herunterladen Inhalt Inhalt Diese Seite drucken

Emerson CSI 6500 Machinery Health Monitor A6110 Schnellstartanleitung Seite 17

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Product Information / Produktinformation A6110
Shaft Vibration Monitor
μP function (watchdog)
Configuration & setting para−
meters
External disable signal
Status channel monitoring
Channel status = no error (OK)
Channel status = error
Channel status = release delayed When switching from error case to OK status or when
Visualization
Green LED on the front panel
Channel status = no error (OK)
Channel status = error
Channel status = release delayed
Channel Clear outputs
Opto−decoupled collector/emitter segments
Channel Clear channel 1, C1C / C1E z26 (collector) / z28 (emitter)
Channel Clear channel 2, C2C / C2E z30 (collector) / z32 (emitter)
Ext. disabled or status = error or
release delayed
Not ext. disabled and status = OK and
not release delayed
Input external disable ES
z22 − for disabling the limit value alarms; e.g. for service work etc.
Disable function
Release
Signal level
WD − OK
C&P − OK
ES
if (voltage_OK = yes)
AND (WD_OK = yes)
AND (C&P_OK = yes)
AND (Sensor signal in the GOOD range)
AND (Ext. disable = no)
If the previous condition is not satisfied
switching on the module a release delay of 15 s (±2 s)
is active
Continuous light
Dark
Flashing light
C−E disabled, max. perm. voltage: 48 V
C−E conducting, max. perm. current: 100 mA
Input LOW = disable the channel monitoring and limit
value formation
Input HIGH or not switched = enable of channel
monitoring and limit value formation
LOW: 0 ... +3 V, HIGH: +13 ... +48 V