Communication Interfaces - Emerson CSI 6500 Machinery Health Monitor Schnellstartanleitung

Dual channel bearing vibration monitor
Vorschau ausblenden Andere Handbücher für CSI 6500 Machinery Health Monitor:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Product Information / Produktinformation A6120
Bearing Vibration Monitor
Alarm visualization
Through one red LEDs each for channel 1 and channel 2
No limit value exceeded or alarm
blocked
ALERT, no DANGER
DANGER
Alarm outputs
Opto−decoupled collector / emitter segments
Alert channel 1 A1−C / A1−E
Danger channel 1 D1−C / D1−E
Alert channel 2 A2−C / A2−E
Danger channel 2 D2−C / D2−E
Maximum value for alarm outputs
Alarm status of the alarm outputs
Open circuit mode / closed−circuit mode
The digital inputs SC−A and SC−D can be selected with external signals.
Switchover ALERT
Switchover DANGER
Switch level
Input resistance

1.6.4 Communication interfaces

Interface RS 232
Front socket for connecting a laptop / computer for configuration and visualization purposes
Round plug connector on the front
side
LED off
LED flashes at 2 Hz (pulse/pause 1:1)
LED on continuously
b26 (collector) / b28 (emitter)
d26 (collector) / d28 (emitter)
b30 (collector) / b32 (emitter)
d30 (collector) / d32 (emitter)
C−E disabled:
max. perm. U
C−E conductive: max. perm. U
Conducting in open circuit mode, disabled in closed−
circuit mode
d24 − SC−A
= HIGH / blank
= open circuit mode
d24 − SC−A
= LOW = closed−circuit mode
z24 − SC−D
= HIGH / blank
= open circuit mode
z24 − SC−D
= LOW = closed−circuit mode
LOW = 0 ... +3 V
HIGH = 13 ... 48 V
> 10 kΩ
Mini DIN socket type TM 0508A/6 for parameterization
cable (included in the operating kit)
Page 18
: 48 V
CE
: 100 mA
CE

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

A6120

Inhaltsverzeichnis