Herunterladen Inhalt Inhalt Diese Seite drucken

Io-Link Basic Knowledge; Protocol; Cycle Time; Communication Parameters - Balluff BOS R254K-UUI-RH10-S4 Konfigurationsanleitung

Vorschau ausblenden Andere Handbücher für BOS R254K-UUI-RH10-S4:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BOS R254K-UUI-RH10-S4
Photoelectric Sensors
2

IO-Link Basic Knowledge

2.1
General
IO-Link integrates conventional and intelligent sensors and
actuators in automation systems and is intended as a
communication standard below classic field buses. Field-
bus-independent transfer uses communication systems
that are already available (field buses or Ethernet-based
systems).
IO-Link devices, such as sensors and actuators, are
connected to the controlling system using a point-to-point
connection via a gateway, the IO-Link master. The IO-Link
devices are connected using commercially available
unshielded standard sensor cables.
Communication is based on a standard UART protocol
with a 24-V pulse modulation in half-duplex operation. This
allows classic three-conductor physics.
2.2

Protocol

With IO-Link communication, permanently defined frames
are cyclically exchanged between the IO-Link master and
the IO-Link device. In this protocol, both process and on
demand data, such as parameters or diagnostic data, is
transferred. The size and the type of the frame and the
cycle time used result from the combination of master and
device features (see communication properties in section
3.2 on page 10).
2.3

Cycle Time

The cycle time used (master cycle time) results from the
minimum possible cycle time of the IO-Link device
(min cycle time, see section 3.2 on page 10) and the
minimum possible cycle time of the IO-Link master. When
selecting the IO-Link master, please note that the larger
value determines the cycle time used.
2.4

Communication parameters

In order to be able to establish a stable communication
connection between master and device, the master
requests some important communication parameters from
the device at the start of communication. Settings for
communication in Preoperate and Operate modes are
influenced by the parameters and the device is clearly
identified.
Communication parameters are described in chapter 4 on
page 28.
6
english
2.5

Process Data Flow

The data transfer is based on the general profile
specification (IO-Link Common Profile 1.0, see Fig. 2-1 for
example).
PDinput data stream (device view)
Transmission
direction
n
n+1
("to master")
39
30
31
24
15
...
Byte 0
Byte 1
7
0
7
0
7
Integer16
UInteger8
"PDV2"
"PDV1"
PVinD 3
PVinD 2
Data type: IntegerT
Data type: UIntegerT
TypeLength: 16
TypeLength: 8
Bit offset: 24
Bit offset: 8
Example PDinput data stream
Fig. 2-1:
Example of a PDinput data flow
The highest value byte (MSB, designated as Byte 0 ) is
transferred first and can be found in the PLC under the
lowest storage address. The lowest value byte (LSB) is
transferred last and has the highest byte number
(designated in Fig. 2-1 as Byte 4).
For word-based data types (> 8 bit) this means that the
byte at the lowest address is the highest value byte, while
the highest address contains the lowest value byte.
In the IODD, the description of the data flow is realized
using the skew descriptors. This skew starts at the right
with the lowest value byte.
Process data variables (in Fig. 2-1: PDV1, PDV2) are
aligned to the byte limits in most cases.
Binary information (BDC) is transferred in the lowest value
byte in most cases.
The process data flow is made up of various process data
objects, which are not only shown in the process data
flow, but are also used for the internal exchange of
information between functions. For example, PdObjects
can be used to offset random binary information in the
function Logic Blocks or to display certain information at
the digital output. Therefore, a unique object ID is assigned
to this individual information, which can be used at
different places.
Process data objects are described in the function
chapters under Process Data.
n+3
n+4
memory address in the PLC
n = baseaddress
8
7
0
Bit offset
Byte 3
Byte 4
0
7
0
Byte stream
Bool
"BDC1_2"
PVinD 1
Data type: Bool
TypeLength: 2
Bit offset: 0

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis