3.3.7 Electrical wiring
3.3.7.1

General check

CAUTION
·When clamping the wiring, use the included clamping material to prevent outside pressure being exerted
on the wiring connections and clamp firmly.
·
When doing the wiring, make sure the wiring is neat and does not cause the control box lid to stick up,
then close the cover firmly. When attaching the control lid, make sure you do not pinch any wires.
·
Outside the machine, separate the weak wiring (remote controller and transmission wiring) and strong
wiring(earth and power supply wiring) at least 50 mm so that they do not pass through the same place
together. Proximity may cause electrical interference, Malfunction , and breakage.
3.3.7.2
Wiring
·Live the sensor cover, remove the front metal plate cover(1 screw), and connect the branch wiring to the terminal block.
(1) Strip wire ends.(15mm)
(2) Match wires with terminal numbers on indoor and outdoor unit's terminal blocks and firmly screw wires
to the corresponding terminals according to the electric wiring diagram.
(3) Connect the power wire to the main terminal.
(4) Connect the earth wire to the hole with a symbol "
(5) Connect the remote control wire to the subsidiary terminal box according to electric wiring diagram.
(6) Pull wires to make sure that they are securely latched up, then retain wires with wire holder.
(7) Make sure that the wires do not come in contact with the metal conduit for the heat exchanger.
:
Note A cable is connected with the terminal for the factory default Remove the cable before wiring
WARNING
·If the fuses burn up, please call the service agency to instead it. Please do not instead by yourself, or
else may result in accident, for example shock.
·Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause
overheating, electrical shock, ore fire.
·Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain
power, etc., from the terminal block. ) Doing so may cause electric shock or fire.