Related information
2.7 Identification of the functional module
4.2.4 Connecting an external switch
6.8.1 Timer function for a digital input
6.9 "Digital inputs/outputs"
6.10 "Signal relay" ("Relay outputs")
6.15 "Predefined setpoints"
6.49 Priority of settings
6.8.1 Timer function for a digital input
Activation delay
The activation delay (T1) is the time between the digital signal and the activation of the selected function.
Range: 0-6000 seconds.
Duration time
Available modes:
Not active
Active with interrupt
Active without interrupt
Active with after-run.
The duration time (T2) is the time which, together with the mode, determines how long the selected function is active.
Range: 0-15,000 seconds.
T3 > T1 + T2
1
T3
2
T1
T2
3
T1
T2
4
T1
Pos.
1
2
3
4
T1
T2
T3
Related information
2.7 Identification of the functional module
6.8 "Digital inputs"
6.9 "Digital inputs/outputs"
6.10 "Signal relay" ("Relay outputs")

6.9 "Digital inputs/outputs"

The inputs and outputs available depend on the functional module fitted in the motor.
44
T3 < T1 + T2
T3
T1
T1
T2
T2
T1
T2
Description
Digital input.
Active with interrupt.
Active without interrupt.
Active with after-run.
Activation delay.
Duration time.
The period of time when the digital input is activated.