Herunterladen Inhalt Inhalt Diese Seite drucken

WIKA A-10 Betriebsanleitung Seite 6

Vorschau ausblenden Andere Handbücher für A-10:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3. Specifications
Specifications
Model A-10
Power supply U
B
GB
1)
not with non-linearity 0.25 % BFSL and 4 ... 20 mA
Signal output and
maximum ohmic load R
R
in Ohm
A
A
Response time
ms
Current consumption
mA
Insulation voltage
Non-linearity
% of span
Adjusted in vertical mounting position with lower pressure connection.
3)
Accuracy
% of span
3)
Including non-linearity, hysteresis, zero point and full scale error (corresponds to
error of measurement per IEC 61298-2).
10
WIKA Operating Instructions Pressure transmitter Model A-10
1)
DC 8 ... 30 V {DC 8 ... 35 V
}
DC 14 ... 30 V {DC 14 ... 35 V} with signal output 0 ... 10 V
5 ± 10 % with signal output 0,5 ... 4,5 ratiometric
4 ... 20 mA, 2-wire
R
≤ (U
– 8 V) / 0.02 A
A
B
0 ... 10 V, 3-wire
R
> 10 k
A
0 ... 5 V, 3-wire
R
> 5 k
A
1 ... 5 V, 3-wire
R
> 5 k
A
0.5 ... 4.5 V, 3-wire
R
> 4.5 k
A
0.5 ... 4.5 V ratiometric R
> 4.5 k
A
{Other signal output on request}
< 4
Signal current (max. 25) for current output
Max. 8 for voltage output signal
2)
DC 500 V
2)
For power supply, use a circuit with energy limitation (EN/UL/
IEC 61010-1, section 9.3) with the following maximum values for
the current: with U
= DC 30 V: 5 A / U
= DC 35 V: 4.2 A. Provide a
B
B
separate switch for the external power supply. Alternative for North
America: The connection may also be made to „Class 2 Circuits" or
„Class 2 Power Units" according to CEC (Canadian Electrical Code)
or NEC (National Electrical Code).
≤ ± 0.25
(BFSL) according to IEC 61298-2
≤ ± 0.5
(BFSL) according to IEC 61298-2
≤ ± 0.5
(with non-linearity 0.25 %)
≤ ± 0.6
(with non-linearity 0.25 % and with signal output 0 ... 5 V)
≤ ± 1.0
(with non-linearity 0.5 %)
3. Specifications
Specifications
Model A-10
Zero offset
% of span
Non-repeatability
% of span
Long-term drift
% of span
Signal noise
% of span
Permissible temperature of
Medium
Ambience
Storage
Rated temperature range
Temperature error in
% of span
rated temperature range
Approvals
CE-conformity
Pressure equipment directive
EMC directive
Shock resistance
g
Vibration resistance
g
Wiring protection
Overvoltage protection
Short-circuit proofness
Reverse polarity protection
Reference conditions
Relative humidity
%
Weight
g
WIKA Operating Instructions Pressure transmitter Model A-10
≤ 0.15 typ., ≤ 0.4 max.,
(with non-linearity 0.25 %)
≤ 0.5 typ., ≤ 0.8 max.,
(with non-linearity 0.5 %)
≤ 0.1
≤ 0.1
according to IEC 61298-2
≤ 0.3
0 ... +80 °C
{-30 ... +100 °C}
32 ... +176 °F
0 ... +80 °C
{-30 ... +100 °C}
32 ... +176 °F
-20 ... +80 °C {-30 ... +100 °C}
-4 ... +176 °F
0 ... +80 °C
+32 ... +176 °F
≤ 1.0 typ., ≤ 2.5 max.
UL, CSA, GOST
This instrument is a pressure accessory as defined by the directive
97/23/EC
2004/108/EC, EN 61 326 Emission (Group 1, Class B) and
Immunity (industrial locations)
500 according to IEC 60068-2-27 (mechanical shock)
10 according to IEC 60068-2-6
(vibration under resonance)
{20 g on request}
DC 32 V; DC 36 V with 4 ... 20 mA
S+ towards 0V
U
towards 0V
B
According to IEC 61298-1
45 ... 75
Approx. 80
GB
{-22 ... +212 °F}
{-22 ... +212 °F}
{-22 ... +212 °F}
11