Mounting and Connection Instructions MB-Secure 4G IP USB / IP USB Extension
3.4

Ethernet attachment cable

An Ethernet-type10/100BASE-T Twisted Pair cable, category 5 or higher quality
must be used. Trade name for example CB-SUTP-3; cat. 5 E; FTP; CV Cat. 5 E,
SFTP.
SUTP = Screened Unshielded Twisted Pair.
3.5

LED indicators on the Ethernet socket

LED 1 and LED 2. There are two LEDs (left LED (yellow) and right LED (green)) on the left and
right of the RJ45 connector.
Left LED
Meaning
(yellow)
off
no data
on
Data communication
LED 3 next to the RJ45 connection indicates the transmission status of the Ethernet connection:
LED 3
Meaning
(green)
off
Half duplex
permanent
Full duplex
green
4

Installation

4.1

Installing the MB-Secure IP USB communication module

The following steps must be performed during installation:
1. Remove the MB-Secure IP USB communication module from the anti-static packaging.
2. If possible, only hold the MB-Secure IP USB communication module by the edge of the cir-
cuit board.
Right LED
(green)
off
on
Module
Meaning
10 Mbps
100 Mbps