Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi Mr. SLIM PEA-M200LA Installationshandbuch Seite 11

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 18
8. Electrical work
d [Fig. 8-5-4]
• Use the [F1] or [F2] button to move the cursor to select the mode number, and
change the setting number with the [F3] or [F4] button.
e [Fig. 8-5-5]
• When the settings are completed, press the [SELECT] button to send the setting
data from the remote controller to the indoor units.
• When the transmission is successfully completed, the screen will return to the
Function setting screen.
8.5.2. For wireless remote controller
[Fig. 8-5-6]
1
CHECK
D
ON/OFF
TEMP
E
3
C
FAN
AUTO STOP
MODE
VANE
AUTO START
CHECK
LOUVER
h
F
A
TEST RUN
min
B
SET
RESET
CLOCK
A Hour button
B Minute button
C TEMP button
D TEMP button
E ON/OFF button
F CHECK button
2
CHECK
CHECK
4
CHECK
CHECK
1. Changing the external static pressure setting.
• Be sure to change the external static pressure setting depending on the duct and
the grill used.
a Go to the function select mode
Press the CHECK button F twice continuously.
(Start this operation from the status of remote controller display turned off.)
is lighted and "00" blinks.
CHECK
Press the TEMP button C once to set "50". Direct the wireless remote controller
toward the receiver of the indoor unit and press the Hour button A.
b Setting the unit number
Press the TEMP button C and D to set the unit number to 01-04 or AL. Direct the
wireless remote controller toward the receiver of the indoor unit and press the
Minute button B.
c Selecting a mode
Enter 08 to change the external static pressure setting using the C and D
buttons.
Direct the wireless remote controller toward the receiver of the indoor unit and
press the Hour button A.
Current setting number:
d Selecting the setting number
Use the C and D buttons to change the external static pressure setting to be
used.
Direct the wireless remote controller toward the sensor of the indoor unit and
press the Hour button A.
e To set the external static pressure
Repeat steps c and d to set the mode number to 10.
f Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit and
press the ON/OFF button E.
Note:
• Whenever changes are made to the function settings after installation or
maintenance, be sure to record the changes with a mark in the "Check"
column of the Function table.
8.5.3. Changing the power voltage setting (Function table 1)
• Be sure to change the power voltage setting depending on the voltage used.
1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)
11