Herunterladen Diese Seite drucken

Daikin FWTSK Installations- Und Bedienungsanleitung Seite 4

Vorschau ausblenden Andere Handbücher für FWTSK:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 5
FWTSK
F
unctions
The temperature sensor is used to:
n Fan control (figure 1: A = Cooling, B = Heating,
C = Water temperature)
n Heating Element (if it is present as heating support)
(figure 2: A = Heating, B = Water temperature)
n Cooling/Heating switching depending on water
temperature (figure 3: A = Summer, B = Winter,
C = Water temperature)
P
robe connestion on controller
n Connect the temperature FWTSK sensor to the
remote control using the supplied cable as accessory
and, in case of prolongations, a shielded cable only.
n The shielding should be connected to the ground on
the fan coil side only.
n The sensor cable (1.5 m) can be cut to measure if
necessary. Never place it near power supply cables.
n Open the controller after removing the screw of the
cover (figure 4)
n Connect the probe to the connector and install it on
the circuit board as indicated in the diagram (figure 5)
n Close the controller
t
emPerature sensor installation
/
/
-
Fwl
m
v
instructions For installation
Use the special copper holder for the temperature sensor
and position it as described below, depending on the type
of installation.
Fan coil units for:
2 pipe systems - without valve: the
sensor must be positioned on the heat
exchanger (figure 6).
4 pipe systems - without valves: the
temperature sensor must be positioned on
the exchanger of the heating circuit
(figure 7).
2
pipe
systems
temperature sensor must be positioned at
the valve inlet, on the branch coming from
the system (figure 8).
4
pipe
systems
temperature sensor must be positioned at
the heating valve inlet, on the branch
coming from the circuit (figure 9).
Installation and operation manual
1
Temperature sensor
-
with
valve:
the
-
with
valves:
the
-
Fwd
instructions For installation
Ex:
Valves
mounted
A
=
Temperature
sensor
B = Temperature sensor for 2 pipe system, C = Air)
n In the case of valveless FWD units for two-
pipe systems, the temperature sensor must
be positioned on the pipe at the exchanger
inlet.
n In the case of valveless FWD units for four-
pipe systems, the temperature sensor must
be positioned on the pipe at the heating
circuit exchanger inlet.
-
Fwb
instructions For installation
Ex: Valves mounted on left side: (figure 11: A = System
pipe to be provided by the user)
n In the case of valveless FWB units for two-
pipe systems, the temperature sensor must
be positioned on the pipe at the exchanger
inlet.
n In the case of valveless FWB units for four-
pipe systems, the temperature sensor must
be positioned on the pipe at the heating
circuit exchanger inlet.
Installation and
operation manual
on
left
side:
(figure
for
4
pipe
system,
FWTSK
Temperature sensor
10:

Werbung

loading