2) Its OFF-position shall be clearly marked;
3) Not to position the equipment so that it is
diffi cult to operate it;
4) The protection current device must be at
least 10A, 250V, curve Type C;
5) This appliance is to be supplied through a
residual current device (RCD) having a rat-
ed residual operating current not exceed-
ing 30 mA.
TRANSPORT, LIFTING
Fan equipment and packaging are protected from
adverse atmosphere, especially water, sand,
dust, vibration and excessive temperature. The
packaging used for this fan has been designed to
support normal transporting conditions.
The fan must always be transported in its orig-
inal packaging. Do not accept delivery if the fan
is not in its original packaging or shows clear
signs of having been damaged.
Do not place heavy weights on the packaging
and avoid impact damage.
Any lifting equipment must be safe and of suit-
able capacity for weight and size. Special at-
tention may be required to ensure fan assem-
bly does not distort or tilt as weight distribution
may vary.
When Fan equipment is carefully lowered or
placed on a surface, be it temporary, during
lifting, positioning, storage or permanent, this
must be a fl at surface to avoid distortion of fan
casing or fan assembly.
STORAGE
Storage must be in a safe, fl at, controlled en-
vironment to prevent damage, especially from
water, sand, dust, moisture, corrosion, temper-
ature. Recommend that duct connections (in-
fl ow and outfl ow) are closed to avoid dust/debris
entering the equipment.
These data may also apply to an installed fan,
which is not put into operation for extended period.
INSTALLATION
Fan equipment should be electrically isolated
and locked out before any work started.
Before any installation work is started, ensure
that fan equipment is correct for application.
Location for installation is solid, level, fl at and
suitable for mounting fan assembly.
Fan should be located in position, and assem-
bled with any accessory equipment supplied,
on relevant mounting, anti-vibration mount-
ings, safety protection guards, on a solid level
base to avoid any distortion and misalignment
and with correct air direction as shown on
nameplate. Fan should then be leveled on any
anti-vibration mountings. Flexible connectors
must be taught to ensure no disruption to air
fl ow, especially on inlet to fan.
Once ready to use, the apparatus must fulfi l
the following Standards:
• Low voltage Directive 2014/35/EU
• Machinery Directive 2006/42/EC
• Electromagnetic Compatibility 2014/30/EU
• ROHS Directive 2011/65/EU
START UP
• Check fan equipment name plate data is ap-
propriate to the location electrical supply,
especially Voltage, Frequency, Phase, Amps,
speed are correct.
• Check earth connections, electrical termina-
tions and terminal box lid, with any seals, if
fi tted, are correct.
• In compliance with Machine Directive, if the
fan is accessible to operators and is a health
and safety risk, adequate protection must be
fi tted, information for safety equipment, in-
cluding guards, can be found in S&P acces-
sories catalogue.
• Check all rotating parts have free, unob-
structed movement.
• Check there are no foreign bodies inside the
fan or that can be drawn into, or fall into fan.
• Check the structure is complete and has no
damage.
• Check installation and area is safe and en-
ergise fan and start motor. Check that the
impeller and airfl ow direction is correct,
check current does not exceed fan equipment
nameplate data.
• After two hours of operation, check that all
fi xings are tight and adjust if necessary.