UL-gerechte Installation

HINWEIS
Das folgende Kapitel wird unabhängig von der Sprache dieser Dokumentation auf-
grund von UL-Anforderungen immer in englischer Sprache abgedruckt.
Field Distributor Model MFE...Z.9...
Field wiring power terminals
Observe the following notes for UL-compliant installation:
Short circuit current rating
Suitable for use on a circuit capable of delivering not more than 200,000 rms symme-
trical amperes when protected by fuses and circuit breakers as described in the tables
below:
Suitable for motor group installation on a circuit capable of delivering not more than
18,000 rms symmetrical amperes when protected by 25 A maximum non-semiconduc-
tor fuses, Class RK5 and delivering not more than 5,000  rms symmetrical amperes
when protected by 25 A maximum inverse time circuit breakers.
For 500 V systems:
The max. voltage is limited to 500 V.
For 250 V systems:
The max. voltage is limited to 240 V.
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below
SCCR: 200 kA/500 V when protected by
Model
Field Distributor
Model MFE...Z.9...
with attached
MM03D – MM15D
SCCR: 200 kA/240 V when protected by
Model
Field Distributor
Model MFE...Z.9...
with attached
MM03D – MM15D
Installationsvorschriften Feldbus-Schnittstellen, Feldverteiler
Use 75 °C copper wire only.
Tighten terminals to 5 – 7 in lbs
Non-semiconductor fuses
(currents are maximum values)
25 A max./500 V min.
Non-semiconductor fuses
(currents are maximum values)
25 A max./250 V min.
Ergänzungen/Korrekturen
Inverse time circuit breakers
(currents are maximum values)
20 A max./500 V min.
Inverse time circuit breakers
(currents are maximum values)
20 A max./250 V min.