can be influenced by the quality of the water and care.
3.6 Rxtarget value: [650 mV]
The disassociation curve of the chlorine value must be observed in accordance with the
pH.
100
80
60
40
20
0
pH 6
The system regulates and doses chlorine via the Redox potential. First set the pH value
in the pool water. Then introduce the required quantity of chlorine to the pool water.
We recommend 0.3-0.6 mg/l measured using the DPD method. Read off the measured
Redox voltage on the control unit and set the setpoint in accordance with the read value.
Since every water has different Redox values (even with the same chlorine
concentration) we are not able to give a basic setting. It will thus not necessarily
correspond to the factory setting of the setpoint. After about 2-3 weeks or every refill,
the setpoint must be compared with the desired chlorine value and adjusted as required
since the effective Redox value is only established when the system is under operation.
If the actual value undercuts the setpoint, the system automatically doses chlorine until
the setpoint is achieved. Then the dosing pump switches off automatically.
3.7 Rx p range: [100 mV]
The numeric value gives the proportional range and thus the regulation slope. The usual
value is 100 mV.
Meaning: With a p range of 100 mV, the dosing pump operates at maximum
performance with a deviation of the measured value compared to the setpoint of Δ 100
mV. When the actual value approaches the setpoint in the p range, the dosing
HCLO
pH 6,5
pH 7,0
36
pH 7,5
pH 8,0
pH 8,5
pH 9,0