INDOOR UNITS INSTALLATION
4.6 SERVICE AND OPERATION SPACE FOR RPI-(4.0~6.0)FSRE
?
N O T E
A service access from the bottom side is required for servicing and maintenance.
4.6.1 Service space for electrical box
b
a
Electrical
box
Service space (mm)
a
b
c
800
300
1474
4.6.2 Service space for lower extraction of the

air filter

Service space (mm)
a
1420
12
PMML0528 rev.1 - 02/2021
c
Top view
d
e
f
100
1000
657
a
b
200
4.6.3 Service space for lateral extraction of the
air filter
e
b
d
a
f
4.6.4 Operation space
!
C A U T I O N
e
If the suction of the indoor unit is through a plenum, there must be no
obstacle less than 1000mm.
If the indoor unit is discharged freely, there must be no obstacle less
than 1000mm.
In case of suction or discharge of the indoor unit through ducts, ducts
must be straight 1000mm span from the unit.
d'
a'
20
b
Service space (mm)
a
b
500
500
Top side
Bottom side
Operation space (mm)
b'
c'
10
10
a'
b'
c'
d'
300