Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi RPI-1.5FSRE Installations- Und Betriebshandbuch Seite 36

Vorschau ausblenden Andere Handbücher für RPI-1.5FSRE:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 75
INDOOR UNITS INSTALLATION
4.3 INSTALLATION SPACE (LOCATION, PRECAUTION, CONDITIONS & ORDER)
!
D A N G E R
Do not install the indoor units outdoors. If installed outdoors, an
electric hazard or electric leakage will occur.
Consider the air distribution from each indoor unit to the space
of the room, and select a suitable location so that uniform air
temperature in the room can be obtained.
Avoid obstacles which may hamper the air intake or the air
discharge flow.
Pay attention to the following points when the indoor units are
installed in a hospital or other places where there are electronic
waves from medical equipment, etc.
- Do not install the indoor units where electromagnetic wave is
directly radiated to the electrical box, remote control cable
or remote control switch.
- Install the indoor units and components as far as practical or
at least 3 meters from the electromagnetic wave radiator.
- Prepare a steel box and install the remote control switch in it.
Prepare a steel conduit tube and wire the remote control cable
in it. Then connect the ground wire with the box and tube.
- Install a noise filter when the power supply emits harmful
noises.
- Do not install the indoor units, outdoor unit, remote control
switch and cable within approximately 3 meters of strong
electromagnetic wave radiators such as medical equipment.
This unit is exclusive non electrical heater type indoor unit. It is
prohibited to install a electrical heater in the field.
Do not put any foreign material into the indoor unit and check to
ensure that none exist in the indoor unit before the installation
and test running. Otherwise a fire or failure, etc., may occur.
Do not perform installation work, refrigerant piping work, drain
pumping, drain piping and electrical wiring connecting work
without referring to the installation manual. If the instructions
are not followed, it may result in a water leakage, an electric
shock, a fire and an injury.
Mount suspension bolts using M10 (W3/8) as size, as shown
below:
For Concrete Slab
150~160mm
I-Beam
Steel
Suspension Bolts
Anchor Bolt
(W3/8 or M10)
!
C A U T I O N
Do not install the indoor units in a flammable environment to avoid a
fire or an explosion.
Check to ensure that the ceiling slab is strong enough. If not strong
enough, the indoor unit may fall down on you.
Do not install the indoor units in a machinery shop or kitchen where
vapor from oil or mist flows to the indoor units. The oil will deposit on
the heat exchanger, thereby reducing the indoor unit performance,
and may deform. In the worst case, the oil damages the plastic parts
of the indoor unit.
To avoid any corrosive action to the heat exchangers, do not install
the indoor units in an acid or alkaline environment.
When lifting or moving the indoor unit, use appropriate slings to avoid
damage and be careful not to damage the insulation material on units
surface.
6
PMML0528 rev.1 - 02/2021
Wooden Bar
(60mm to 90mm Square)
Nuts
Concrete
washers
Wooden
Sling Bolt
Beam
(W3/8 or M10)
4.3.1 Suspended unit
Install the indoor unit with a proper clearance around it paying
careful attention of installation direction for the piping, wiring and
maintenance working space.
Mount suspension bolts using M10 (W3/8) or greater are also
recommended, as size, as shown below:
DIMENSIONS TO INSTALL SUSPENSION BOLT (mm)
Models
RPI-(1.5~2.0)FSRE
RPI-(2.5~3.0)FSRE
RPI-(4.0~6.0)FSRE
150 to 160mm
Steel
Square
I-Beam
a
790
1124
1514
For concrete slab:
Insert
(100 to 150kg)
Concrete
Anchor bolt
(W3/8 or M10)
For steel beam:
Suspension bolt
(W3/8 or M10)
b
544
544
544

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis