Fault diagnosis
Fault
Urinal does not flus-
hing after each use
S. 73
Possible cause
Sensor module not
working
Flush system in the
wrong mode
Fault rectification
Check the sensor position used for
the existing urinal as per separate
installation instructions.
Check correct sensor location.
The sensor must attached to the
surface of the ceramic, facing in
the direction of the arrow. The
product label must be legible.
Check the functioning of the sen-
sor module (diagnosis mode, see
separate operating instructions or
check via app).
Check the correct setting of the in-
tended base sensitivity of the sen-
sor module for the installed urinal
(base sensitivity,
see "Base sensiti-
vity", page 63
or via app).
Make sure that hybrid mode and
stadium mode are deactivated.
When hybrid mode or stadium
mode is activated, the system flus-
hes only at stipulated fixed inter-
vals.