5.5

Connecting the motor

Prematic AG, Märwilerstrasse 43, 9556 Affeltrangen www.prematic.ch
Danger of death if the electrical installation has
not been done professionally.
The electrical installation must only be done by
a qualified electrician observing EN 60204. The
operating company has to provide the main switch.
For operation on the frequency converter, observe
the manufacturer's operating instructions for the
frequency converter.
a) The drive consisting of the components motor
and frequency converter. The mechanical and
electric connection between motor and frequen-
cy converter is already assembled on delivery.
The frequency converter is parameterised with
the basic adjustment settings.
b) Connect the frequency converter (Fig. 2/V)
according to the operating instructions
610.00260.40.000 or with the attached con-
nection diagram. For the observance with the
protection class IP 65 shall be provided suitable
cable glands resp. shutters. The electric network
connection values are to be taken from the type
label (Fig. 4) of the frequency converter.
NOTICE
Power supply
The electric supply of the frequency converter must
to be in accordance with the following values:
• Input voltage
• Input frequency
• Suitable network configurations
www.gd-elmorietschle.com © Gardner Denver Schopfheim GmbH, Gardner Denver Deutschland GmbH
DANGER
3 AC 400 V -15 %
bis 460V + 10 %
47 bis 63 Hz ± 0%
Tel. 071 918 60 60, Mail: v-g@prematic.ch
Installation
TN / TT
17
|