Herunterladen Diese Seite drucken

Fronius Symo 10.0-3-M Installation Seite 3

Vorschau ausblenden Andere Handbücher für Symo 10.0-3-M:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
WARNING! An electric shock can be fatal. Danger due to grid voltage and DC voltage from solar modules that are exposed to light.
– Ensure that both the AC side and the DC side of the inverter are de-energised before carrying out any connection work.
– Only an authorised electrical engineer is permitted to connect this equipment to the public grid.
– The DC main switch is only to be used to de-energise the power stage set. The connection area is still live when the DC main switch is swit-
ched off.
– Ensure that the power stage set and connection area are disconnected from one another before carrying out any maintenance or service
tasks.
– The power stage set, which is enclosed in a separate housing, must only be disconnected from the connection area when in a de-energized
state.
– Maintenance and servicing in the power stage set of the inverter must only be carried out by Fronius-trained service technicians.
WARNING! An electric shock can be fatal. Danger due to residual voltage in capacitors. Wait for the capacitors to discharge. The discharge
time is five minutes.
WARNING! An inadequate ground conductor connection can cause serious injury or damage. The housing screws provide a suitable ground
conductor connection for grounding the housing and must NOT be replaced by any other screws that do not provide a reliable ground conduc-
tor connection.
WARNING! Shoddy workmanship can cause serious injury and material damage. A surge protective device must only ever be installed and
connected by a qualified electrical engineer. Follow the safety rules. Ensure that both the AC side and the DC side of the inverter are de-ener-
gised before carrying out any installation and connection work.
CAUTION! Risk of damage to the inverter from dirt or water on the terminals and contacts of
the connection area.
– When drilling, ensure that terminals and contacts in the connection area do not become dirty or wet.
– Without a power stage set, the mounting bracket does not conform to the protection class of the inverter as a whole and so must not be
installed without the power stage set.
– The mounting bracket should be protected from dirt and moisture during installation.
CAUTION! Risk of damage to the inverter as the result of incorrectly tightened terminals. Incorrectly tightened terminals can cause heat da-
mage to the inverter that may result in a fire. When connecting AC and DC cables, ensure that all the terminals are tightened to the specified
torque.
CAUTION! Risk of damage to inverter from overload.
– The maximum amperage when connecting to a single DC terminal is 33 A.
– Connect the DC+ and DC- cables to the DC+ and DC- terminals on the inverter, taking care to ensure that the polarity is correct.
– The maximum DC input voltage must not exceed 1000 V DC.
CAUTION! Risk of damage to inverters and other live photovoltaic system components due to poor or unprofessional installation. Poor or
unprofessional installation can cause overheating of cables and terminal connections and result in arcs. These can cause heat damage, which in
turn may lead to fires.
Observe the following when connecting AC and DC cables:
– Tighten all terminals to the torque specified in the Operating Instructions
– Tighten all grounding terminals (PE / GND), including free ones, to the torque specified in the Operating Instructions
– Do not overload cables
– Check cables for damage and verify that they are laid correctly
– Take note of the safety instructions, Operating Instructions and any local connection regulations
Using fastening screws, always screw the inverter firmly to the mounting bracket to the torque
specified in the Operating Instructions. Ensure that the fastening screws are tight before starting the inverter!
NOTE! Protection class IP66 is only applicable if:
– The inverter is permanently attached to the mounting bracket with screws.
– The cover for the data communication area is permanently attached to the inverter with screws
– Protection class IP20 applies to the mounting bracket with no inverter or venting duct.
NOTE! The solar modules connected to the inverter must comply with the IEC 61730 Class A standard.
NOTE!
– Ensure that the grid neutral conductor is grounded. This may not be the case for IT grids (insulated grids with no grounding); it will then not
be possible to use the inverter.
– In order to use the inverter, the neutral conductor must be connected. A neutral conductor that is too small may adversely affect the inver-
ter feeding energy into the grid. The neutral conductor must therefore be the same size as the other live conductors.
Observe the manufacturer's connection, Installation and Operating Instructions at all times. To reduce the hazard potential to a minimum,
perform all installation and connection work carefully according to the instructions and regulations. Refer to the device Operating Instructions
/ Installation Instructions for the tightening torques to be used at the relevant terminal connections.
FR: AVERTISSEMENT!
Les erreurs de commande et les erreurs en cours d'opération peuvent entraîner des dommages corporels et matériels graves. L'installation et
la mise en service de l'onduleur ne doivent être effectuées que par du personnel formé à cet effet et dans le cadre des dispositions techniques.
Ne travailler avec l'appareil que lorsque tous les documents mis à disposition en annexe, imprimés et en ligne, ont été lus et compris ! Les
modules solaires exposés à la lumière fournissent la tension à l'onduleur. Ce document ne décrit pas toutes les possibilités de configurations
système. Le soussigné, Fronius International GmbH, déclare que l'équipement radioélectrique du type Fronius Symo est conforme à la directive
2014/53/UE. Le texte complet de la déclaration UE de conformité est disponible à l'adresse internet suivante: www.fronius.com
AVERTISSEMENT ! Une décharge électrique peut être mortelle. Danger en raison de la tension du secteur et de la tension DC des modules
solaires exposés à la lumière.
– Avant toute opération de raccordement, veiller à ce que les côtés AC et DC en amont de l'onduleur soient hors tension.
– Le raccordement fixe au réseau électrique public doit être réalisé uniquement par un électricien agréé.
– L'interrupteur principal DC sert exclusivement à la mise hors courant de l'étage de puissance. Lorsque l'interrupteur principal DC est dé-
connecté, la zone de raccordement reste sous tension.
– Les opérations de maintenance et de service doivent être exécutées uniquement lorsque l'étage de puissance et la zone de raccordement
sont séparés.
– Le bloc indépendant de l'étage de puissance ne doit être séparé de la zone de raccordement que si l'ensemble est hors tension.
– Les opérations de maintenance et de service dans l'étage de puissance de l'onduleur doivent être exécutées uniquement par du personnel de
service formé par Fronius.
AVERTISSEMENT ! Une décharge électrique peut être mortelle. Danger en raison de la tension résiduelle de condensateurs. Attendre l'expirati-
on de la durée de décharge des condensateurs. Cette durée est de 5 minutes.

Werbung

loading