Technical information / Functioning / Parameters
Switch-off point: Lower limit value at which the output changes its switching status.
rP1 ... rP4 are active only if binary mode is not active (bin = OFF)
setting range
LK3022
LK3023
LK3024
Dependence between rPx and SPx:
1. rPx is always lower than SPx. The unit only accepts values which are lower than SPx..
2. If the difference between rPx and SPx is small (approx. 3 x steps), increasing the switch-on
point also increases the switch-off point (the difference SPx - rPx remains constant).
3. If the difference between rPx and SPx is great, rPx remains at the set value even if SPx is
increased.
4. If SPx is set to the minimum value and then increased, rPx is also set to the minimum
value and increased proportionally.
Hysteresis
Window function
Page 30
All manuals and user guides at all-guides.com
cm
2,0 ... 20,0
3,5 ... 41,0
5,0 ... 60,0
Values for OFS = 0; with OFS > 0 the OFS value is added to these values.
The hysteresis keeps the switch-
ing state of the output stable if
the level varies about the preset
value. When the level is rising,
the output switches when the
switch-on
point
reached (SPx); when the level is
falling again, the output switches
back when the switch-off point
(rPx) has been reached.
The hysteresis can be adjusted:
First the switch-on point is set, then the switch-off point with the
requested difference.
The window function enables the
monitoring of a defined accept-
able range. When the level varies
between the switch-on point
(SPx) and the switch-off point
(rPx), the output is switched (win-
dow
function/NO)
switched (window function/NC).
The width of the window can be
set by means of the difference
between SPx and rPx. SPx =
upper value, rPx = lower value.
inch
0,8 ... 7,8
1,2 ... 16,0
2,0 ... 23,5
P
SP
rP
has
been
1
0
1
0
acceptable range
P
SP
rP
or
not
1
0
1
0
in steps of
0,5cm / 0,2inch
0,5cm / 0,2inch
1,0cm / 0,5inch
hysteresis
t
Hno
Hnc
t
Fno
Fnc

Werbung