7.4 Alarm diagrams; datalogger type ...H2
7.4.1 Connector 3; white
Alarm with local power supply (12VDC)
Alarm with power supply and cable break monitoring
Alarm with power supply monitoring
Alarm without power supply and cable break monitoring
7.4.2 Connector 4; red
Alarm with external power supply
D-EL-6003Bk
Manual
ECOLOG-NET
- Requires 12VDC supply for signaling
- Alarm triggered by threshold violation
- Switching load max. 42VAC or VDC; 500mA
- Alarm triggered by threshold violation or
failure of external 12VDC power supply
or cable break
- Switching load max. 42VAC or VDC; 500mA
- Alarm triggered by threshold violation or
failure of external 12VDC power supply
- Switching load max. 42VAC or VDC; 500mA
# Relay is activated as soon as 12VDC supply voltage is present
- Alarm triggered by threshold violation
- Datalogger does not require external power
supply
- Switching load max. 24VDC; 200mA
- Alarm triggered by threshold violation
- Switching load max. 24VDC; 200mA