Brightness Value Calibration; Pir Evaluation - Niko SWISS GARDE 300 Applikationsbeschreibung

Vorschau ausblenden Andere Handbücher für SWISS GARDE 300:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2524X/2525XCH
Transmission of the lux value in case of
change of
Cyclical transmission of the light value
Lux value of the threshold for switching
Hysteresis
Object value for ON
Object value for OFF
Transmission filter

3.5. Brightness value calibration

Calibration
AD calibration value
Lux value

3.6. PIR evaluation

8
EN
The parameters for object 8
(Brightness threshold switch, 1 bit) and object 9
This parameter allows the lux value + change to be sent via object 9 (brightness value) if the set threshold is exceeded. Values from 10 lux up to 1800 lux and "OFF" can be
set. The set value of change refers to the set threshold.
Values from 5 seconds to 30 minutes and „OFF" can be set.
Can be set from 10 lux to 2000 lux
Can be set from 5 lux to 200 lux
Selection: "ON" or "OFF"
Selection: "OFF" or "ON"
Selections: "ON and OFF"; "neither ON nor OFF"; "ON only"; "OFF only"
"NO": Factory calibration is enabled (default value)
Reset to factory calibration: This is possible at any time with the setting "NO" and thereafter the reprogramming of the detector.
"YES": This option opens the following two additional windows:
Read AD calibration value (at
object 10) in the ETS and enter it in the window.
Attention: use type 7.001 unsigned 2 byte counter in the read/send value menu! The AD value read-out then appears in the Value received menu (e.g. 739 pulses).
Measure reference brightness with lux meter and enter corresponding value.
See also description of "AD calibration value" on §4.4 for further details.
(Brightness value, 2 bytes) can be set in the Brightness / Threshold menu.