4.5. OBJECTS FOR CONSTANT LIGHT CONTROL

4.5.1. OBJECT 16 CONSTANT LIGHT - SWITCH ON/OFF
Input 1 bit
This input allows the constant light controller to be switched ON and OFF (Object).
Alternatively the constant light controller can be activated by motion detection on the light or the HVAC channel.
4.5.2. OBJECT 17 CONSTANT LIGHT - RELATIVE DIMMING
Input 4 bit
Using this object, the current value is changed with relative dimming steps of 1%.
Using a KNX push button, light can be dimmed and set to a new brightness level.
The new light value can then be displayed in Lux on a KNX touch panel through object 9: brightness value.
Important: In the menu constant light
(not to the flash memory)!
Note: This new target value remains stored in RAM as long as there are people present in the scanned area. After switching the light channel off and back on again, the set point stored in ETS is adopted once again.
If the newly changed set point are definitely taken over, set the parameter Keep changed set point to YES (see also section 3.8 Constant light parameter page 18)
4.5.3. OBJECT 18 CONSTANT LIGHT – PRESET DIMMING
Input 1 Byte
With this object the user can define a new dim set point in % over the bus.
4.5.4. OBJECT 20 CONSTANT LIGHT - FORCE CONTROL
Input 1 bit
In accordance to the parameters force output at ON and force output at OFF, various options can be selected: no reaction, minimum brightness, maximum brightness
4.5.5. OBJECT 21 CONSTANT LIGHT - SCENE
Input 1 byte
Scene selection input. 8 adjustable scenes can be selected via ETS.
This object has no switch function but only changes the brightness setpoint values.
4.5.6. OBJECT 22 CONSTANT LIGHT - OUTPUT CHANNEL 1
Output 1 byte
This is the constant light control signal (% brightness) for the dimming actuator of lighting 1
4.5.7. OBJECT 23 CONSTANT LIGHT - OUTPUT CHANNEL 2
OUTPUT 1 byte
This is the constant light control signal for the dimming actuator of lighting 2.
The lux value is equal to channel 1 +/- offset.