Grid Monitoring - ABB PVS800 Handbuch

Zentralwechselrichter
Vorschau ausblenden Andere Handbücher für PVS800:
Inhaltsverzeichnis

Werbung

15
No.
Name/Value

44 GRID MONITORING

44.01
NAMU GRIDMON
MODE
NONE
ALARM
FAULT
44.02
UNDER FREQ 1 LIM 100 = 1
45...65 Hz
44.03
UNDER FREQ 2 LIM 100 = 1
45...65 Hz
44.04
UNDER FREQ 1
TIME
0...33554.4 s
44.05
UNDER FREQ 2
TIME
0...33554.4 s
44.06
OVER FREQ 1 LIM
45...65 Hz
44.07
OVER FREQ 2 LIM
45...65 Hz
44.08
OVER FREQ 1 TIME 100 = 1 s Defines a trip time for over frequency fault 1.
0...33554.4 s
44.09
OVER FREQ 2 TIME 100 = 1 s Defines a trip time for over frequency fault 2.
0...33554.4 s
Update notice
FbEq
Description
Parameters related to internal grid monitoring.
Note: Group 44 is write-protected. It can be write-enabled by giving
a password with parameter
Defines the usage mode of the internal grid monitoring. Grid
monitoring is based on the voltage measurement via the NAMU
board.
0
Internal grid monitoring is disabled.
1
Internal grid monitoring is enabled. If grid voltage and/or frequency
are outside limits that are defined by parameters 44.02...44.17, a
corresponding alarm is created and the inverter continues to
operate.
2
Internal grid monitoring is enabled. If grid voltage and/or frequency
are outside limits that are defined by parameters 44.02...44.17, a
corresponding fault is created and the inverter stops.
Defines a trip limit for under frequency fault 1. If the grid frequency
Hz
(signal
02.18 GRID
the time delay in parameter
inverter will generate an alarm or a fault according to parameter
44.01 NAMU GRIDMON
Trip limit 1
Defines a trip limit for under frequency fault 2. If the grid frequency
Hz
(signal
02.18 GRID
time delay in parameter
will generate an alarm or a fault according to parameter
NAMU GRIDMON
Trip limit 2
100 = 1 s Defines a trip time for under frequency fault 1.
Trip time 1
100 = 1 s Defines a trip time for under frequency fault 2.
Trip time 2
100 = 1
Defines a trip limit for over frequency fault 1. If the grid frequency
Hz
(signal
02.18 GRID
the time delay in parameter
inverter will generate an alarm or a fault according to parameter
44.01 NAMU GRIDMON
Trip limit 1
100 = 1
Defines a trip limit for over frequency fault 2. If the grid frequency
Hz
(signal
02.18 GRID
the time delay in parameter
inverter will generate an alarm or a fault according to parameter
44.01 NAMU GRIDMON
Trip limit 2
Trip time 1
Trip time 2
16.03 PASS
CODE.
FREQUENCY) is below this setting longer than
44.04 UNDER FREQ 1
MODE.
FREQUENCY) is below this setting longer than
44.05 UNDER FREQ 2
MODE.
FREQUENCY) exceeds this setting longer than
44.08 OVER FREQ 1
MODE.
FREQUENCY) exceeds this setting longer than
44.09 OVER FREQ 2
MODE.
Def.
NONE
47.5 Hz
TIME, the
47.5 Hz
TIME, the inverter
44.01
0.1 s
0.1 s
51.5 Hz
TIME, the
51.5 Hz
TIME, the
0.1 s
0.1 s
T
I
R
R
R
R
R
R
R
R