About this document
1
About this document
These instructions describe the installation and commissioning of the GEZE Boxer E-ISM guide rail.
In conjunction with:
à Geze Boxer size 2-4
à Geze Boxer size 3-6
Version small hinge distance (1130-1300mm): Opening angle of doors: approx. 100°.
Version small fixed leaf (min. leaf width 420mm plus space requirement of the locking system): Opening angle of
doors: moving leaf approx. 120° / fixed leaf approx. 100°.
1.1
Product description
This slide rail is approved for installation on double-leaf fire and smoke protection doors. The system contains
electrical hold-open devices for both door leaves and an integrated closing sequence control. If the moving leaf is
closed with the door leaves opened and engaged in the electrical hold-open device, the electrical hold-open de-
vice of the fixed leaf is swiched off. The moving leaf remains in its waiting position until the fixed leaf is closed and
releases the moving leaf via the closing sequence control. In case of power interruption, the electrical hold-open
device is triggered and the doors closes automatically.
If a double leaf smoke or fire protection door can be opened via the passive leaf, without opening the active leaf
up to the minimal waiting position of the sequence control, a preferably adjustable carry bar such as the GEZE
CBflex must be used to ensure the functionality of the door sequence control unit.
1.2
Related documents
Additional documents for the installation and connection of the system are supplied with every component.
Please follow these instructions.
For mounting of the door closer, refer to the Boxer mounting instructions.
2
Key to symbols
Warning
In these instructions, warnings are used to warn against material damage and injuries.
X
Always read and observe these warnings.
X
Follow all instructions marked with the warning symbol and the word WARNING.
Warning
Warning
symbol
DANGER
CAUTION
Further symbols used in these instructions
Important information and technical notes are emphasised to illustrate the correct operation.
Symbol
Meaning
means "Important note"
means "Additional information"
Symbol for a user action. Here you have to take an action.
X
X
Observe the sequence if there are several action steps.
3
Product liability
According to the definition of manufacturer's liability for his products in the Product Liability Act, the informati-
on contained in this brochure are to be followed. Ignoring this information absolves the manufacturer from his
liability.
4
Safety instructions
à Installation, commissioning and repairs must be performed by a specialist.
à Use only GEZE original parts for repair work.
à Unauthorised modifications of the system excludes GEZE from the liability for any resulting damage.
à When used in fire and smoke barriers, all local regulations should be observed.
à Please observe the document "Instructions for Installation, Commissioning, Operation and Maintenance of the
GEZE Hold-Open Device FA GC".
à Restrict the opening angle of the doors by a door stopper.
GB 2
Meaning
Danger for people.
Non-observance can result in death or serious injuries.
Information to prevent damage to property and to understand and optimise workflow.
E-ISM Boxer