Herunterladen Inhalt Inhalt Diese Seite drucken

Air Purging - Toshiba RAV-GM2241AT8-E Installationsanleitung

Vorschau ausblenden Andere Handbücher für RAV-GM2241AT8-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 15
Simultaneous triple
Allowable pipe length (m)
Total length
Branch piping
• ℓ1 + ℓ2
• ℓ2
Outdoor unit
• ℓ1 + ℓ3
• ℓ3
• ℓ1 + ℓ4
• ℓ4
Maximum
Maximum
GM224
50
20
GM280
50
20
Outdoor unit
Main pipe
Gas side
Liquid side
GM224
Ø28.6
GM280
Ø28.6
Indoor Unit
Outdoor Unit
Simultaneous double twin
Allowable pipe length (m)
Branch
Branch
Total length
piping
piping
•ℓ1 +ℓ2 +ℓ4
Outdoor
•ℓ4
•ℓ4 +ℓ2
•ℓ1 +ℓ2 +ℓ5
unit
•ℓ5
•ℓ5 +ℓ2
•ℓ1 +ℓ3 +ℓ6
•ℓ6
•ℓ6 +ℓ3
•ℓ1 +ℓ3 +ℓ7
•ℓ7
•ℓ7 +ℓ3
Maximum
Maximum
Maximum
GM224
50
15
GM280
50
15
Outdoor unit
Main pipe
Gas side
Liquid side
GM224
Ø28.6
GM280
Ø28.6
Indoor Unit
Outdoor Unit
4
125-EN
Height difference (m)
Branch piping
Indoor-outdoor H
• ℓ3 – ℓ2
• ℓ4 – ℓ2
Indoor unit:
Outdoor unit:
• ℓ4 – ℓ3
Upper
Upper
Maximum
10
30
30
10
30
30
Pipe diameter (mm)
Branch piping
Gas side
Liquid side
Ø12.7
Ø15.9
Ø9.5
Ø12.7
Ø15.9
Ø9.5
Figure of Simultaneous triple
Indoor Unit
Indoor Unit
4
2
3
1
Height difference (m)
Branch piping
Indoor-outdoor H
• (ℓ4 +ℓ2) – (ℓ5 +ℓ2)
• (ℓ4 +ℓ2) – (ℓ6 +ℓ3)
• (ℓ4 +ℓ2) – (ℓ7 +ℓ3)
Outdoor
Indoor unit:
• (ℓ5 +ℓ2) – (ℓ6 +ℓ3)
unit:
Upper
• (ℓ5 +ℓ2) – (ℓ7 +ℓ3)
Upper
• (ℓ6 +ℓ3) – (ℓ7 +ℓ3)
Maximum
20
6
30
30
20
6
30
30
Pipe diameter (mm)
Branch piping
Gas side
Liquid side
ℓ2, ℓ3: Ø15.9
ℓ2, ℓ3: Ø9.5
Ø12.7
ℓ4, ℓ5, ℓ6, ℓ7: Ø12.7
ℓ4, ℓ5, ℓ6, ℓ7: Ø6.4
Ø12.7
ℓ2 to ℓ7: Ø15.9
ℓ2 to ℓ7: Ø9.5
Figure of Simultaneous double twin
Indoor Unit
Indoor Unit
Indoor Unit
5
6
7
2
3
1
– 63 –
6

Air purging

 Airtight Test
Indoor-indoor
(Δh)
After completing the refrigerant piping work, perform an airtight test. Connect a nitrogen gas cylinder and
pressurize the pipes with nitrogen gas as follows to conduct the airtight test.
0.5
0.5
Low pressure gauge
Number of bent
portions
10 or less
Charge port
10 or less
Gas leak check
Step 1....Pressurize to 0.5 MPa (5 kg/cm
Step 2....Pressurize to 1.5 MPa (15 kg/cm
Step 3....Pressurize to 4.15 MPa (42 kg/cm
(However, note that when the ambient temperature differs during pressurization and after 24 hours, the pressure
will change by approximately 0.01 MPa (0.1 kg/cm2G) per 1°C, so this should be compensated.)
If the pressure drops in steps 1 through 3, check the connections for leakage.
Check for leaks with foaming liquid, etc., take steps to fix the leaks such as brazing the pipes again and tightening the flare
nuts, and then perform the airtight test again.
Indoor-
indoor
* After the airtight test is completed, evacuate the nitrogen gas.
(Δh)
 Air purge
0.5
0.5
With respect to the preservation of the terrestrial
environment, adopt "Vacuum pump" to purge air
(Evacuate air in the connecting pipes) when installing
Number of bent
the unit.
portions
• Do not discharge the refrigerant gas to the
atmosphere to preserve the terrestrial environment.
10 or less
• Use a vacuum pump to discharge the air (nitrogen,
etc.) that remains in the set. If air remains, the
10 or less
capacity may decrease.
For the vacuum pump, be sure to use one with a
backflow preventer so that the oil in the pump does not
backflow into the pipe of the air conditioner when the
pump stops.
(If oil in the vacuum pump is put in an air conditioner
including R32, it may cause trouble with the
refrigeration cycle.)
High pressure gauge
CAUTION
Gauge manifold
V
V
L
H
Never use oxygen, flammable gas, or noxious gas for
the airtight test.
Pressure reducing
valve
Nitrogen gas
2
G) for 5 minutes or longer.
2
G) for 5 minutes or longer.
2
G) for 24 hours. ........................ Micro leaks can be discovered.
Compound
pressure gauge
–101 kPa
(–76 cmHg)
Handle Low
Charge hose
(For R32 or
R410A only)
Charge port
(Valve core
(Setting pin))
Major leaks can be discovered.
Pressure gauge
Gauge manifold
valve
Handle High
(Keep fully closed)
Charge hose (For R32 or
R410A only)
Vacuum pump
adapter for
backflow
prevention
(For R32 or
R410A only)
Vacuum
pump
Packed valve at gas side
126-EN