Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Location - Toshiba RAV-GM2241AT8-E Installationsanleitung

Vorschau ausblenden Andere Handbücher für RAV-GM2241AT8-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 15
 Installation location
WARNING
Install the outdoor unit properly in a location that
is durable enough to support the weight of the
outdoor unit.
Insufficient durability may cause the outdoor unit to
fall, which may result in injury.
This outdoor unit has a weight of about 142 kg. Pay
special attention when installing the unit onto a wall
surface.
CAUTION
Do not install the outdoor unit in a location that is
subject to combustible gas leaks.
Accumulation of combustible gas around the outdoor
unit may cause a fire.
Install the outdoor unit in a location that meets the
following conditions after the customer's consent
is obtained.
• A well-ventilated location free from obstacles near
the air intakes and air discharge.
• A location that is not exposed to rain or direct
sunlight.
• A location that does not increase the operating noise
or vibration of the outdoor unit.
• A location that does not produce any drainage
problems from discharged water.
Do not install the outdoor unit in the following
locations.
• A location with a saline atmosphere (coastal area) or
one that is full of sulfide gas (hot-spring area)
(Special maintenance is required).
• A location subject to oil, vapor, oily smoke, or
corrosive gases.
• A location in which organic solvent is used.
• Places where iron or other metal dust is present.
If iron or other metal dust adheres to or collects on
the interior of the air conditioner, it may
spontaneously combust and start a fire.
• A location where high-frequency equipment
(including inverter equipment, private power
generator, medical equipment, and communication
equipment) is used (Installation in such a location
may cause malfunction of the air conditioner,
abnormal control or problems due to noise from such
equipment).
• A location in which the discharged air of the outdoor
unit blows against the window of a neighboring
house.
• A location where the operating noise of the outdoor
unit is transmitted.
• When the outdoor unit is installed in an elevated
position, be sure to secure its feet.
• A location in which drain water poses any problems.
115-EN
CAUTION
1
Install the outdoor unit in a location where the
discharge air is not blocked.
2
When an outdoor unit is installed in a location
that is always exposed to strong winds like a
coast or on the high stories of a building,
secure normal fan operation by using a duct or
wind shield.
3
When installing the outdoor unit in a location
that is constantly exposed to strong winds
such as on the upper stairs or rooftop of a
building, apply the windproofing measures
referred to in the following examples.
1. Install the unit so that its discharge port faces the
wall of the building.
Keep a distance 500 mm or more between the unit
and wall surface.
500 mm
Wall
2. Consider the wind direction during the operational
season of the air conditioner, and install the unit so
that the discharge port is set at a right angle relative
to the wind direction.
Strong wind
Strong wind
• When using an air conditioner under low outside
temperature conditions (Outside temp. -5 °C or
lower) in COOL mode, prepare a duct or snow hood
so that it is not affected by the snow.
<Example>
Snow hood
Snow hood
– 58 –
116-EN

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis