DRAIN

/ TROUBLESHOOTING

6
TROUBLESHOOTING

6.1 ACTIVITIES FOR TROUBLESHOOTING

Fault
Emergency flap won't
activate
Backflow flap will not
close/open
Backflow stop is leaky
38
Cause(s)
Emergency flap is not correctly
inserted in the insertion part
Emergency flap or the insertion part
is not correctly installed
Emergency flap is clogged up with
deposits (dirt)
Emergency flap is damaged
Backflow flap is clogged up with
deposits (dirt)
Backflow flap is damaged
Housing cover is not installed
correctly
Cover seal is damaged
Red locking screw from the housing
cover is loose
Seal of the red locking screw is
damaged
Remedy/ies
Check the correct position and
Î
installation of the emergency flap
in combination with the insertion
part
Inspecting and cleaning the
Î
backflow unit,
Section 5.2
Replace the emergency flap
Î
Inspecting and cleaning the
Î
backflow unit,
Section 5.2
Replace the backlow flap
Î
Remove the housing cover and
Î
install it again,
Replace the housing cover
Î
immediately
Tighten the red locking screw
Î
with 5 – 6 N·m.
Replace the seal or the locking
Î
screw
Section 5.2