5.9 Auxiliary heating
In addition to the heating effect achieved using the refrigerant circuit, the controller can handle other sources of
heating such as electric heaters and a hot water coil with an OK signal to a boiler or a burner.
The logic featured in the controller is set up at the factory, based on the unit configuration.
The function to enable heating and the operating logics can be customised.
The parameters concerned are shown in the table.
Parameter
Min
STH57
0
STH58
10.0
STH59
0.0
STH60
0.0
STH61
0
STH62
0
STH91
0
STH93
0.0
STH94
0.0
STH95
0
STH96
0
We reserve the right to make changes without any prior notice.
UATYA
4P645203-1
Max
UM
Description
1
-
Auxiliary heating - Summer oper. - Type of temperature control
35.0
°C
Auxiliary heating - Summer oper. - Setpoint
25.0
°C
Auxiliary heating - Summer oper. - Proportional - Temperature offset
25.0
°C
Auxiliary heating - Summer oper. - Proportional - Activation differential
100
%
Auxiliary heating - Summer oper. - Proportional - Minimum request
100
%
Auxiliary heating - Summer oper. - Proportional - Maximum request
1
-
Auxiliary heating - Winter oper. - Type of temperature control
25.0
°C
Auxiliary heating - Winter oper. - Proportional - Temperature offset
25.0
°C
Auxiliary heating - Winter oper. - Proportional - Activation differential
100
%
Auxiliary heating - Winter oper. - Proportional - Minimum request
100
%
Auxiliary heating - Winter oper. - Proportional - Maximum request