Herunterladen Inhalt Inhalt Diese Seite drucken

Heating Element - Daikin FWEC1 Installations- Und Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 37
The display shows fan speed (with indication of "automatic"
logic if proper) enabled or selected (in case of stand-by fan)
Extra low speed
Low speed
Medium speed
High speed
NB: if the active speed is different from the one selected by
the user (in the case of a forced override), pressing the
button
once will cause the latter to be displayed;
pressing again will change this setting.
VALVE
The controller can govern 2 or 3-way On/OFF type valves with
actuator featuring 230 V.
OPENING
The valve opening is controlled according to the operating
setpoint and air temperature setpoint
COOLING
HEATING
WATER CONTROL
The checking of water temperature to enable valve opening
is a function that concerns only configurations with 3-way
valves and heating element. In such configurations the water
temperature will be checked in the following cases:
 H eating with heat element: operation of the heating element
will force the fan to switch on; it is therefore necessary to
prevent excessively cold water from passing through the
unit.
 P ost-ventilation due to switching off of the heating element:
this function will be maintained until the set time has
elapsed, even if the operating mode is changed. During
post-ventilation the water temperature enabling signal will
coincide with the one seen for fan operation.
DISPLAY
The active valve indication on the display will be shown by
the symbol
Installation and operation manual
6

HEATING ELEMENT

The electrical heating element is a device used to provide
support where necessary in the heating mode.
SELECTION
If provided for in the configuration, the heating element can
be selected in the heating mode by pressing the Sel
ACTIVATION
If use of the heating element is selected by the user, it will be
activated on a call from the thermostat based on the room
temperature
NB: switching it on will force the fan on as well
WATER CONTROL
HEATING
Air temp.
Enabling of the heating element is tied to the water temperature.
The related enabling logic is described below
The enabling signal will not be given if the water sensor is
Air temp.
either not present or disconnected
DISPLAY
The display will show the following information
 h eating element selected by the user: steadily lit
 a ctive heating element: flashing symbol
Water temp.
ON
OFF
Standard electronic controller
key.
Air temp.
Water temp.
symbol
FWEC1
FC66002763

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis