6.1
Preparation of the
installation site
The installation of the device must be carried out in a
suitable place in order to allow the normal use and
adjustment operations, together with ordinary and
extraordinary maintenance to be performed.
Therefore it is important to allow for the necessary
working space by referring to the dimensions shown in
Fig. 2.
Y1
X1
X2
≥500 kg
Fig. 2 – Minimum spaces
X1
X2
Model
mm
Mm
EKHH2E200AAV3
650
650
EKHH2E200BAV33
EKHH2E260AAV3
EKHH2E260PAAV3
Moreover, the premises must:
Have adequate water and power supply lines;
Be available and ready for connection to the
condense drain;
Be available and ready with adequate discharge
pipes in case of damage caused to the boiler or
actuation of the safety valve or breakage of
pipes/connections;
Have containment systems in case of serious
water leaks;
Be sufficiently lit (where appropriate);
Not measure less than 20 m
3
Be frost-proof and dry.
WARNING!
In order to avoid the propagation of mechanical
vibrations, do not install the equipment on floor
slabs with wooden beams (e.g. in lofts).
Installation and user manual

6.1.1 Securing to the floor

To secure the product to the floor, fasten the supplied
brackets as shown in fig. 3.
X3
Fig.3 - Fastening brackets
Then secure the unit to the floor with the aid of suitable
plugs not supplied, as shown in fig. 3a.
X3
Y1
mm
mm
200
300
Fig.3a - Securing to the floor
6.2
Apart from the space indicated in paragraph 6.1, the
heat pump requires adequate ventilation.
It is necessary to create a dedicated air duct as
indicated in the following illustration (Fig. 4a and 4b).
;

Ventilation connection