Tabelle 29. Herabstufung der Betriebstemperatur - Technische Daten
Herabstufung der Betriebstemperatur
Bis zu 35 °C (95 °F)
35 °C bis 40 °C (95 °F bis 104 °F)
40 °C bis 45 °C (104 °F bis 113 °F)
Verwandte Verweise
Erweiterte Betriebstemperatur
Identifier
Version
Status

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the level of particulates or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility
of the customer.
Tabelle 30. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Tabelle 31. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
ANMERKUNG:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
on page 42
GUID-CC72FD5A-E02D-4BC7-A091-30EAFCFB47B0
2
To be translated
Technische Daten
Maximale Temperatur verringert sich um 1 °C/300 m
(1 °F/547 Fuß) oberhalb von 950 m (3.117 Fuß).
Maximale Temperatur verringert sich um 1 °C/175 m (1 °F/
319 Fuß) oberhalb von 950 m (3.117 Fuß).
Maximale Temperatur verringert sich um 1 °C/125 m (1 °F/
228 Fuß) oberhalb von 950 m (3.117 Fuß).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
ANMERKUNG:
This condition applies only to data center
environments. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in
environments such as an office or factory floor.
ANMERKUNG:
Air entering the data center must have
MERV11 or MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
ANMERKUNG:
This condition applies to data center and
non-data center environments.
● Air must be free of corrosive dust.
● Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
ANMERKUNG:
This condition applies to data center and
non-data center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
Technische Daten
41